Verified by manufacturer over a year ago
Ultra-low radiation fire and smoke shutter.
Suitable for escape path protection, warehouse dividing walls, basement carparks (with cars adjacent to the barrier), openings in external walls and fire compartment walls, construction of proscenium walls and servery openings in smoke-proof walls for healthcare and residential care buildings.
Fibershield ULR120 is an ultra-low radiation fire and smoke shutter. Some of its features include:
Material | Manufacturer guidanceStandard material is galvanised steel. Stainless steel optional. |
Shape | Rectangle |
Length | Bespoke |
Width | Bespoke |
Height | Bespoke |
Warranty description | One year |
Uniclass | |
SpecPack | 08330 Roller Shutter Doors 10240 Grilles and Screens |
NATSPEC National Classification System | 0454 Overhead Doors 1002 Fire Services Design and Install |
SpeedSpec | 08330 Roller Shutter Doors |
Performance | |
Fire resistance level | |
Standard | To AS 1530.4. |
Value | -/120/- (minimum). |
Smoke leakage | |
Standard | To EN 12101-1. |
Value | ≤ 25 m³/h.Manufacturer guidanceRefers to fabric permeability only. |
Fire hazard properties | |
Standard | To AS/NZS 1530.3 and AS 3837. |
Group number | 1.Manufacturer guidanceTested in accordance with AS 3837. |
Spread of flame index | Manufacturer guidanceTested in accordance with AS 1530.3. |
Durability | 2000 open-close cycles. |
Closing time | 150 mm/s (nominal). |
Time delay for deployment | Manufacturer guidanceUpon receipt of alarm or power outage. |
Time delay for rewind | Manufacturer guidanceUpon reset of the Fire Indicator Panel. |
Fail safe close | Manufacturer guidanceGravity fail safe. |
Battery back-up | Manufacturer guidanceProvisioned by the control box as an optional extra. |
Curtain | |
Size and shape (maximum) | Manufacturer guidanceAvailable in sizes up to 12 m W x 6 m H. Contact local manufacturer for specific dimension needs. |
Colour | Silver. |
Head box | |
Size | 250 mm H x 190 mm D (for curtain heights up to 2 m).290 mm H x 235 mm D (for curtain heights up to 6 m).Manufacturer guidanceWidth varies depending on specified curtain size. Contact local manufacturer for specific dimension needs. |
Finish | |
Coating | Powder-coated.Guidance for specification option: Standard powder coating finish. |
Side guides | |
Size | 105 mm W x 74 mm D. |
Finish | |
Coating | Powder-coated.Guidance for specification option: Standard powder coating finish. |
Controls | Control box.Guidance for specification option: Requires one 240 V, 10 A power supply and an alarm signal through a normally closed dry contact. |
Integral accessories | Alarm signal.Guidance for specification option: Should be in the form of a normally closed dry contact. A localised smoke or heat detector may also be used. |
Fire barrier | To AS 1905.2. Manufacturer guidanceRefers to Fire Shutter performance data. |
Heat | ≤ 2.5 kW/m² at 500 mm. Manufacturer guidanceRefers to radiant heat. Calculated at 30 minutes into the Standard Fire Test (AS 1530.4). |
Box weight | 30 kg/m of system width (for curtain heights up to 3 m). 35 kg/m of system width (for curtain heights up to 4 m). 50 kg/m of system width (for curtain heights up to 6 m). Manufacturer guidanceRefers to system weight. |
MaximumWorkingPressure | 100 Pa (fully closed curtain up to 50 m²). 50 Pa (fully closed curtain up to 100 m²). Manufacturer guidanceRefers to maximum pressure resistance. |
Optional features | Battery back-up. Rewind switches. Guidance for specification option: Rewind switches are optionally available for direct connection to the control box. Curtain retraction will be based on a set timer. |
Installation | To be installed by Smoke Control approved installer network. |
Country of material origin | Germany |
Country of product manufacture | Australia |