Suitable for use with loads operating at any power factor (leading or lagging) up to 0.9.
-
-
Input
-
-
-
Nominal voltage
Three-phase 400 V a.c.
-
-
Voltage tolerance
±1%.
-
-
Frequency
50 Hz. ±2%., 60 Hz. ±2%.
-
-
Power factor
>0.99 at full load.
-
-
Input current distortion (THDi)
≤0.9% at full load.
-
-
Inrush current
Maximum 1.8 sec at full load.
-
-
Inverter output
-
-
-
Rated output apparent power
25 kV·A.
-
-
Nominal voltage
380/220 V., 400/230 V., 415/240 V.
-
-
Voltage tolerance
±1%.
-
-
Voltage waveform
Sinusoidal in both normal and stored energy mode of operation.
-
-
Voltage distortion
<1% with linear load.
-
-
Nominal frequency
50 Hz., 60 Hz.
-
-
Frequency tolerance
+/- 2%., +/- 4%.
-
-
Overload capability
120% continuous.
-
-
Output power factor (minimum)
1.
-
-
Crest factor
>3:1.
-
-
Integral bypass operation
-
-
-
Automatic transfer of the load to the bypass source under the following conditions
Fault condition.
-
-
Re-transfer of the load from the bypass source
Automatic unless under manual control or fault conditions are present.
-
-
Maintenance bypass
Not required., Required.
-
-
Batteries
-
-
-
Location
Separate battery enclosures.
-
-
Type
Lead-acid.
-
-
Voltage
12 V.
-
-
Battery supply d.c. circuit breaker with overload and short circuit protection
Required.
-
-
Battery recharge time
-
-
-
To 100% capacity
Within 12 hours.
-
-
Controls, indicators and alarms
-
-
-
LCD display
3.5” User Graphical LCD Interface.
-
-
Audible alarms
-
-
-
Type
Integral alarm within UPS enclosure.
-
-
Activation and reset
Activated by any fault condition. Continuous output until fault cleared or alarm silenced. Silencing of the alarm must not clear LED status indication.
-
-
Communications and signalling
SNMP adaptor.
-
-
Enclosure
-
-
-
Material and construction
-
-
-
Type
Welded carbon steel. Assemble to prevent distortion when the complete enclosure is lifted or transported.
-
-
Finish
Epoxy powder-coated.
-
-
Colour
RAL 7024 Graphite grey.
-
-
Cable entry with removable gland plates
For top entry cables., For bottom entry cables., For front entry cables.