Fire Curtain - Vertical Flameshield 8524 (S) Fire and Smoke Curtain - Fire and Smoke Curtain
Fire Curtain - Vertical Flameshield 8524 (S) Fire and Smoke Curtain - Fire and Smoke Curtain
Fire Curtain - Vertical Flameshield 8524 (S) Fire and Smoke Curtain - Fire and Smoke Curtain

Verified 3 months ago

A1S Group

Verified 3 months ago

A1S Group

Verified 3 months ago

A1S Group
Summary
An automatic vertical fire curtain barrier that has 120 minutes integrity and 85 minutes radiation, tested to BS EN 1634-1 and BS EN 1634-3 in accordance with BS 8524-1.
-
-
Application

The Flameshield 8524 (S) Fire and Smoke curtain is designed for multiple applications such:

  • Protected means of escape.
  • Atriums.
  • Lobbies.
  • Receptions.
  • Openings in walls.
  • Egress.
  • Corridor separation.
  • Boundary protection.
  • Escalators.
  • Stairs.
  • Lifts and lift lobbies.
  • Hospitals.
  • Schools.
  • Hotels.
  • High Buildings.
  • Offices.
  • Military sites.
  • Retail.
  • Stadia.
  • Museums and galleries.
  • Prisons.
  • Train stations.
  • Airports.
  • Warehouses.
  • Factories.
  • Nurseries.
  • Shopping centres.
  • Restaurants.
-
-
Description

This automatic vertical fire curtain barrier from A1S, has 120 minutes integrity and 85 minutes radiation at 15kw/m2. It has been tested to BS EN 1634-1 and BS EN 1634-3 in accordance with BS 8524-1.

The fire curtain is comprised of a carbon steel barrel and motor incorporating an attached fabric curtain. The barrel deflection conforms to the necessary British Standard BS 6323-5, the fabric can withstand temperatures in excess of 1000°C and the two section T-shape bottom rail allows smooth operation of the fire curtain. The fire barrier is powered by an internal 24 V d.c electric motor that has all of the applicable safety standards.

Fully compliance-tested and include fail-safe features enabling the fire curtain to operate, even if there’s a power failure. 

The Flameshield 8524 (S) Fire and Smoke curtain is an excellent product if aesthetics of the building need to be maintained. The fire curtain's end plates, guides and head boxes can be finished with specialist RAL colours.

Egress switches, access switches, obstruction warnings, and heat and smoke alarms are fully tested to the ancillary equipment Annex H as stipulated by BS 8524-1.

Features and benefits:

  • Gravity fail safe closes without mains power.
  • Internal battery back up.
  • Provides smoke control.
  • Lightweight slimline compact design.
  • Two stage closing operation. Split drop and delay drop.
  • Compliance tested to maintain building fire safety and integrity in accordance with BS 8524-1.
  • Installed in accordance with BS 8524-2.
  • Can be hidden neatly above the ceiling line to assist the building design and aesthetics.
  • Voice warning devices available.
  • Fully resets after fire test without the need for engineers to attend.
  • Low maintenance costs.
  • Timed delay closing.

All fire curtains are tested and approved by Warrington Fire Research Centre and Exova. Tests are fully compliant and in accordance with BS 8524-1 / BS EN 1634-1 for fire and radiation (radiation and tenability replaces the insulation zone) and BS EN 1634-3 for smoke containment. The construction and manufacture is in accordance with Warrington test WF 341175 (deflection), WF 347098 (smoke) WF 399170 (motor test) WF 399421 (surface spread of flame, BS EN 476-6 and BS EN 476-7). 

https://a1sgroup.com/fire-and-smoke-curtains

-
-
Product certifications
-
-
Digital objects
-
-
Color
Other
-
-
Finish
Powder-coated
-
-
Material
Carbon steel
-
-
Shape
Rectangle
-
-
Length
Bespoke
-
-
Width
10000 mm
-
-
Height
10000 mm
-
-
Warranty description
One year
-
-

Specification

Standards
-
-
-
Barrier assemblies
To BS 8524-1, BS EN 1634-1 and BS 1634-3.
-
-
Test standards
Vertical, horizontal and angled to BS EN 1634-1.
-
-
Third-party certification
IFCC 1542 and IFCC 3425. Warrington Fire Report 340986.
-
-
Performance
-
-
-
Pressure and impact
Tested to BS 5234-1 (Clause 5.2 BS 8524-1) Warrington Test number WIL 403113 Issue 3.
-
-
Durability class
C1.
-
-
Smoke containment
No smoke seals.
-
-
Fire resistance
120 minutes integrity classified to EW60.
-
-
Reaction to fire
To BS 476-6 and BS 476-7.
-
-
Deployment
Immediate deployment from receipt of alarm signal. Split and delay drop facilities with timed hold.
-
-
Activation
Specialist panel with internal battery back up and modified motor. Activation on receipt of relevant alarm signal.
-
-
Accessories
Partial Drop., Emergency Retract., BMS Interface., Single Photo Cell., Audio / Visual / Spoken Warning Unit., Egress switches., Access switches.
-
-

Additional properties

Radiation
85 minutes at 15 kW/m².
-
-
Fabric
Fire rated fabric 0.54 mm thick stainless steel wire reinforced, aluminium pigmented and fire retardant polymer.
-
-
Barrel
Carbon steel tube.
-
-

Sustainability data

Material
Carbon steel
-
-