An automatic vertical overlapping fire curtain barrier that has 120 minutes integrity and 74 minutes radiation, tested to BS EN 1634-1 and BS EN 1634-3 in accordance with BS 8524-1.
An automatic vertical overlapping fire curtain barrier that has 120 minutes integrity and 74 minutes radiation, tested to BS EN 1634-1 and BS EN 1634-3 in accordance with BS 8524-1.
Color
Other
Other
Finish
Powder-coated
Powder-coated
Material
Carbon steel
Carbon steel
Shape
Rectangle
Rectangle
Length
Bespoke
Bespoke
Width
Bespoke
Bespoke
Height
Bespoke
Bespoke
Warranty description
One year
One year
Specification
Standards
To BS 8524-1, BS EN 1634-1, BS 476-6 and -7, BS EN 12605, BS EN 14600, BS EN 13501-2 and BS EN 16034.
To BS 8524-1, BS EN 1634-1, BS 476-6 and -7, BS EN 12605, BS EN 14600, BS EN 13501-2 and BS EN 16034.
Fire curtains are formed from a fire rated fabric 0.54 mm thick stainless steel wire reinforced, with a specially formulated aluminum pigmented and fire retardant polymer which provides a heat reflecting surface as well as other properties for smoke and fire.
Fire curtains are formed from a fire rated fabric 0.54 mm thick stainless steel wire reinforced, with a specially formulated aluminum pigmented and fire retardant polymer which provides a heat reflecting surface as well as other properties for smoke and fire.
Barrel
Fire curtain barrels are manufactured from carbon steel tube, tube size dependent on the overall size of the unit and deflection calculated to conform to British Standards.
Fire curtain barrels are manufactured from carbon steel tube, tube size dependent on the overall size of the unit and deflection calculated to conform to British Standards.