NBS Source
I'm a manufacturer

Compare variants

FLH - FlexLine Resistive - Steam Humidifier Range
FLH - FlexLine Resistive - Steam Humidifier Range
FLH - FlexLine Resistive - Steam Humidifier Range

Verified 1 month ago

CAREL

Verified 1 month ago

CAREL

Verified 1 month ago

CAREL
Summary
Steam humidifiers which consist of a basic model that can be expanded to create an individual humidification solution.
Third party certification
Digital objects
-
-
Color
White, Silver
-
-
Finish
Powder-coated
-
-
Material
Metal
-
-
Shape
Other
-
-
Length
320 mm, 420 mm
-
-
Width
540 mm, 640 mm, 1170 mm
-
-
Height
535 mm, 695 mm, 785 mm
-
-
Warranty description
One year
-
-

Specification

Electrical supply type
Three phase, 380–415 V a.c., 50/ 60 Hz.
-
-
Steam source
Resistive boiler (heater elements).
-
-
Material
Galvanized metal housing.
-
-
Access doors for maintenance
Manufacturer's standard.
-
-
Accessories
Not required., Standard manifolds., Fan blower, VU10 up to 10 kg/h., Fan blower, VU30 up to 30 kg/h., Steam hose., Fogmaker for steam bath., Steam jet nozzle for steam bath., Remote display for steam bath., Temperature sensor for steam bath.
-
-

Additional properties

Dimensions
1170 x 785 x 420 mm.
-
-
Weight
80 kg.
-
-
Network type
Modbus RTU., BACnet.
-
-
Steam
Rated production: 91–108.6 kg/h.
-
-
Power consumption
2 x 34.1–40.7 kW.
-
-
Connections
Steam: 4 x 40 mm diameter.
Water fill: 3/4”.
Water drain: 2 x Ø1 1/4“.
-
-
Pressure
Outlet pressure limits: 0–1500 Pa.
-
-
Cylinders
Standard cleanable cylinder., SuperFlush and HyFlush., HyCool., HyFlush and HyCool.
-
-
Conditions
Operating: 5 to 40°C, to not exceed 80% relative humidity.
-
-
Ingress protection
IP20.
-
-
Model
FLH-T (HVAC) - Resistive., FLH-TSPA (Wellness/ SPA) - Resistive.
-
-
Water
Fill:
· Temperature limits: <40°C.
· Water pressure limits: 1 to 10 (bar).
· Conductivity limits: 125 to 1250 μS/cm.
-
-
Fan
Four blower, type VU30.
-
-