NBS Source
I'm a manufacturer

Compare variants

Medipower™ Triple Cabinet IPS - Medical IT Power Supply
Medipower™ Triple Cabinet IPS - Medical IT Power Supply
Medipower™ Triple Cabinet IPS - Medical IT Power Supply

Verified 3 days ago

Brandon Medical Co Ltd

Verified 3 days ago

Brandon Medical Co Ltd

Verified 3 days ago

Brandon Medical Co Ltd
Summary
Isolated power supply for group 2 medical locations.
Product certifications

Self-declared

Digital objects
-
-
Color
Grey
-
-
Finish
Powder-coated
-
-
Material
Steel
-
-
Shape
Rectangle
-
-
Length
350 mm
-
-
Width
800 mm
-
-
Height
1700 mm
-
-

Specification

Standards
-
-
-
Generally
In accordance with BS 7671, HD 60364-7-710, and HTM 06-01.
-
-
Safety
To BS EN 60601-1 and BS EN 61558-2-15.
-
-
Monitoring
To BS EN IEC 61557-1, BS EN 61557-8 and BS EN 61557-9.
-
-
Service conditions
-
-
-
Treatment locations
Suitable for medical group 2.
-
-
Clinical risk
To HTM 06-01, category 5 areas.
-
-
Configuration
-
-
-
Isolating transformer
4 kV·A.
-
-
Distribution
-
-
-
Number of ways
Available in functional blocks of 6, up to a maximum of 96.
-
-
Surge protection
Not required., Required.
-
-
Automatic transfer
From primary to secondary within 0.5 s.
-
-
Provision for maintenance
Not required., Break before make bypass switch.
-
-
Communications
CANbus (Controller Area Network bus).
-
-
Integration with other systems
-
-
-
Secondary supply
Not required., Integrated uninterruptible power supply (UPS).
-
-
Enclosure
-
-
-
Arrangement
Modular.
-
-
Mounting type
Floor-mounted., Wall-mounted.
-
-
Material
Mild steel.
-
-
Finish
Powder-coated.
-
-
Colour
Light grey (RAL 7035).
-
-
Ingress protection (minimum)
IP41.
-
-
Ventilation arrangement
Three fans.
-
-
Ancillary products
Local alarm panels (LAP).
-
-

Additional properties

Configuration
Triple cabinet (TIPS).
-
-
Components
Incoming isolator.
Control and monitoring device - ILT.
-
-
Dimensions
1700 x 800 x 350 mm.
-
-
Air flow
42 m³/hr per IPS channel.
-
-
Protective earth bars
100 A.
-
-
Circuit breakers
24.
-
-
Rated frequency
50–60 Hz.
-
-
Input voltage
230 V a.c.
-
-
Current rating
17.4 A.
-
-
Power dissipation
Heat power dissipation no-load: <36 W.
Heat power dissipation 100%-load: <138 W.
-
-
Efficiency
96%.
-
-
Weight
52 kg.
-
-
Supply
Typical MCB Supply (A): C32 or D25.
Typical MCCB Supply (A): AF63/ AT30.
-
-
Accessories
Not required., MCB tripped monitoring., Network gateway., MODbus interface., Primary side outgoing RCBO’s (Type – 2C,25).
-
-

Sustainability data

Country of product manufacture
United Kingdom
-
-
Material
Steel
-
-