Summary
Monolithic uninterruptible power supplies.
Color
Grey, Black
-
-
Finish
Powder-coated
-
-
Material
Metal
-
-
Shape
Rectangle
-
-
Length
Bespoke
-
-
Width
Bespoke
-
-
Height
Bespoke
-
-

Specification

Standards
To BS EN IEC 62040-1 and BS EN 62040-3.
-
-
Test requirements
Submit type test certificates.
-
-
Mode of operation
Online.
-
-
Configuration
Parallel with bypass.
-
-
Efficiency
-
-
-
Overall (minimum)
Manufacturer's standard.
-
-
Eco mode (minimum)
98%.
-
-
Load compatibility
Suitable for use with loads operating at any power factor (leading or lagging) up to 0.9.
-
-
Input
-
-
-
Nominal voltage
Three-phase 400 V a.c.
-
-
Voltage tolerance
+20% -25% at full load.
-
-
Frequency
45–60 Hz.
-
-
Power factor
Manufacturer's standard.
-
-
Inrush current
Manufacturer's standard.
-
-
Inverter output
-
-
-
Rated output apparent power
10 kV·A.
-
-
Nominal voltage
Single-phase 220 V a.c., Single-phase 230 V a.c., Single-phase 240 V a.c.
-
-
Voltage tolerance
±1%.
-
-
Voltage waveform
Sinusoidal in both normal and stored energy mode of operation.
-
-
Voltage distortion
<1% with linear load / <3% with non-linear load.
-
-
Nominal frequency
50 Hz., 60 Hz.
-
-
Frequency tolerance
0.05%.
-
-
Overload capability
110% for 60 min; 125% for 10 min; 150% for 1 min.
-
-
Output power factor (minimum)
1.
-
-
Crest factor
3:1.
-
-
Galvanic separation between input and output
Required.
-
-
Integral bypass operation
-
-
-
Automatic transfer of the load to the bypass source under the following conditions
Fault condition.
-
-
Re-transfer of the load from the bypass source
Automatic unless under manual control or fault conditions are present.
-
-
Maintenance bypass
Not required.
-
-
Batteries
-
-
-
Location
Separate battery enclosures.
-
-
Type
VRLA AGM., GEL., NiCd., Li-ion., SuperCaps.
-
-
Voltage
12 V.
-
-
Controls, indicators and alarms
-
-
-
LCD display
UPS status LEDs - graphic display.
-
-
Audible alarms
-
-
-
Type
Integral alarm within UPS enclosure.
-
-
Activation and reset
Activated by any fault condition. Continuous output until fault cleared or alarm silenced. Silencing of the alarm must not clear LED status indication.
-
-
Communications and signalling
RS 232 port.
-
-
Enclosure
-
-
-
Ingress protection (minimum)
IP20.
-
-
Material and construction
-
-
-
Type
Welded carbon steel. Assemble to prevent distortion when the complete enclosure is lifted or transported.
-
-
Finish
Epoxy powder-coated.
-
-
Colour
RAL 7016 Anthracite grey.
-
-
Cable entry with removable gland plates
For top entry cables., For bottom entry cables., For front entry cables.
-
-
Ventilation arrangement
-
-
-
Type
Actively controlled fan ventilation.
-
-
Fan failure alarms
Required.
-
-
Noise emission
-
-
-
Sound pressure level in normal mode (maximum)
60 dBA at 1 m.
-
-

Sustainability data

Material
Metal
-
-