Tmax XT moulded case circuit breakers guarantee an extremely high performance level while being progressively smaller in size, simple to install and able to provide increasingly better safety.
Color
Grey
-
-
Material
Metal, Plastic
-
-
Shape
Rectangle
-
-
Length
70 mm, 82.5 mm, 145 mm, 103.5 mm, 166 mm, 178 mm
-
-
Width
76.2 mm, 101.6 mm, 120 mm, 140 mm, 105 mm, 186 mm, 210 mm, 280 mm
-
-
Height
130 mm, 150 mm, 160 mm, 205 mm, 268 mm
-
-
Warranty description
One year
-
-
Specification
Standards
To IEC 60947-2.
-
-
Third-party certification
Declaration of Conformity - CE; GL certificate; LR certificate.
-
-
Rated operational current (Ie)
160 A.
-
-
Number of poles
Three.
-
-
Rated operational voltage (Ue)
690 V a.c./ 500 V d.c.
-
-
Rated insulation voltage (Ui)
800 V.
-
-
Rated impulse withstand voltage (Uimp)
8 kV.
-
-
Rated frequency
50 Hz., 60 Hz.
-
-
Rated ultimate short circuit breaking capacity (Icu)
100 kA (220/ 230/ 240 V a.c.);
70 kA (380/ 415 V a.c.);
65 kA (440 V a.c.);
50 kA (500 V a.c.);
35 kA (525 V a.c.);
10 kA (690 V a.c.);
70 kA (250 V d.c. two poles in series; 500 V d.c. three poles in series).
-
-
Rated service short circuit breaking capacity (Ics)
80 kA (220/ 230/ 240 V a.c.);
52.5 kA (380 V a.c.);
37.5 kA (415 V a.c.);
32.5 kA (440 V a.c.);
25 kA (500 V a.c.);
17.5 kA (525 V a.c.);
5 kA (690 V a.c.);
52.5 kA (250 V d.c. two poles in series; 500 V d.c. three poles in series).
-
-
Utilization category
Manufacturer's standard.
-
-
Protection
-
-
-
Type
Thermal/ magnetic.
-
-
Characteristics
Manufacturer's standard.
-
-
Settings
Setting range: 160/ 136/ 112 A.
-
-
Measurement
Manufacturer's standard.
-
-
Adjustment
Rotary dials.
-
-
Suitable for isolation
Required.
-
-
Method of installation
Manufacturer's standard.
-
-
Service conditions
Manufacturer's standard.
-
-
Ingress protection (minimum)
Manufacturer's standard.
-
-
Connections
-
-
-
Position
Front.
-
-
Configuration
Bolt.
-
-
Accessories
-
-
-
Additional properties
Net weight
1.1 kg.
-
-
Durability
Electrical: 120 cycles per hour; 8000 cycle. Mechanical: 240 cycles per hour; 25 000 cycle.
-
-
Rated instantaneous short-circuit current setting (Ii)