To DIN VDE 0100-710, DIN VDE 0100-718, ÖVE/ÖNORM E 8007, IEC 60364-7-710, DIN EN 61508-1, IEC 61508-1, DIN EN 61508-2, IEC 61508-2, DIN EN 61508-3, IEC 61508-3, DIN EN 60947-6-1, IEC 60947-6-1.
-
-
Method of controlling transfer
Automatic.
-
-
Operating sequence
I-O-II.
-
-
Rated operational voltage (Ue)
230 V.
-
-
Rated insulation voltage (Ui)
250 V.
-
-
Rated operational current (Ie)
63 A.
-
-
Rated operational frequency
50 Hz, 60 Hz.
-
-
Number of poles
Two.
-
-
Terminals
Screw-type terminals.
-
-
Controls
-
-
-
Type
Integral to switch.
-
-
Display type
Liquid crystal display (LCD).
-
-
Illuminated display to indicate the following conditions
Line 1: Measured values of mains voltage and frequency; Switch position of the automatic transfer switching device; Line 2: Measured values of mains voltage and frequency; Display of the load in the IT system in %.
-
-
User-adjustable functions
Changeover; Voltage; Current; Relay; Digital input; Data logger; Language; Interface; Clock; Password.
-
-
Features
Autom. changeover test; Manual changeover test; Last changeover test; Generator test; Test communication.
-
-
Enclosure
-
-
-
Ingress protection (minimum)
To DIN EN 60529, IP40.
-
-
Material
Polycarbonate.
-
-
Colour
Yellow.
-
-
Additional properties
Accessories
ATICS-BP-2-63A-SET Bypass switch set.
-
-
Sustainability data
Country of product manufacture
Germany
-
-
Material
Polycarbonate
-
-
Recyclability
Can be returned to manufacturer for disposal under WEEE regulations.
Login to download a report. Data within the report includes; general product data, sustainability data, and EPDs.
This product includes self-declared certifications provided directly by the manufacturer.
While not verified by an Environmental Product Declaration (EPD), these declarations outline key environmental performance data shared by the manufacturer.
This property contains differences between variants. Double check the values to ensure this variant is still appropriate for you.