Verified by manufacturer 6 months ago
Speed fan control panel, built and tested to provide a method of operating a single 400 V three phase 50 Hz duty/ standby fan arrangement.
Suitable for smoke and environmental ventilation applications.
Speed fan control panel, built and tested to provide a method of operating a single 400 V three phase 50 Hz duty/ standby fan arrangement.
Features and benefits:
Color | Grey Guidance for specification option: RAL 7035. Blue Guidance for specification option: RAL 5020. |
Finish | Powder-coated |
Material | Steel |
Shape | Rectangle |
Length | 400 mm |
Width | 1200 mm |
Height | 1400 mm |
Uniclass | |
CAWS | S92/410 Sprinkler alarm panels S92/410 Control panels |
Enclosure | |
Ingress protection (minimum) | IP55.Guidance for specification option: Internal and external fully weatherproofed. |
Material | Steel. |
Finish | Externally polyester powder-coated. |
Colour | Light grey panel (RAL 7035); ocean blue canopy (RAL 5020). |
Doors and panels | |
Form | Right-angle return construction with square edges and corners and concealed hinges. |
Swing | 90°. |
Isolator | |
Type | Switch-disconnector. |
Rated operational voltage (Ue) | 400 V. |
Rated operational frequency | 50 Hz. |
Rated short-time withstand current (Icw) | 1–50.6 A.Guidance for specification option: Current draw between 1 to 50.6 A depending on either quiescent state or system activated state and associated fan Full Load Current (FLC): 15–22 kW: 21 to 38.5 A FLC. |
Cable entry | Bottom. |
Internal cable zones | Sufficient to allow cabling to be neatly routed and terminated. |
Terminals | |
Mounting | Internal.External. |
Humidity | 10–90% (non-condensing). |
Operating temperature range | -5 to 40°C. Guidance for specification option: Internally climate controlled via cooling fan and heater. |
Dimensions | 1400 x 1200 x 400 mm. |
Battery back-up | PLC backup battery 2 x 12 V 12.0 Ah sealed lead-acid batteries. Guidance for specification option: Batteries not included. |
Country of product manufacture | United Kingdom |