Description

Envirotec Air Handling Units (AHUs) provide a powerful air output and are particularly suited to a wide range of uses in multiple sectors.

The Enviropac unit can also be delivered as a "Flatpack" that can then be assembled on site by our engineers overcoming many installation issues and constraints of existing buildings.

Unit are available with variety of accessories such as VSD's and full control packages.

These can be used both internally and externally to the building.

Features and benefits:

  • Up to 92% of energy recovery efficiency.
  • Available in 14 sizes.
  • Durable and tight structure.
  • Reliable components.
  • Smart controls.
  • User safety.
  • Highly aesthetic and ergonomic handles securing perfect tightness of inspection panels.
  • Aluminium structural posts with additional sealing blade and thermal break.

General information

Color

Other

Finish

Zinc plated

Powder-coated

Material

Steel

Aluminium

Shape

Rectangle

Length

Bespoke

Width

Bespoke

Height

Bespoke

Warranty description

One year

Other

Manufacturer guidance

Air Handling Units are critical to the operation of a building and should always be maintains by a competent service provider. If Envirotec is selected for this service there are options available to extend the warranty of the product.

Uniclass

Pr_60_65_03_86 Supply air-handling unitsPrimary

Specification data - Supply air-handling units

Duty

-

Air volume

From 1100 m³/h to 100 000 m³/h.

External resistance

-

Manufacturer guidance

Consult manufacturer and insert requirements.

Discharge velocity

-

Manufacturer guidance

Consult manufacturer and insert requirements.

Sound power level

-

Manufacturer guidance

Consult manufacturer and insert requirements.

Environment

External.
Internal.

Casing construction

-

Standard

To BS EN 1886.

Details

-

Manufacturer guidance

Consult manufacturer and insert requirements.

Casing class

D1.

Leakage class of casing

L1.

Filter bypass leakage

To BS EN 1886.

Thermal performance of casing

-

Thermal transmittance

T2.

Thermal bridging

TB3.

Acoustic insulation of casing

To BS EN 1886.

Mechanical safety

To BS EN 1886.

Material

Galvanized sheet steel.

Finish

Powder-coated.

Air-handling unit feet

Steel base frame.

Special requirements

-

Manufacturer guidance

Consult manufacturer and insert requirements or omit.

Arrangement

-

Manufacturer guidance

Consult manufacturer and insert requirements.

Method of support

Aluminium structural posts.

Components

-

Dampers

-

Damper control

Manual.

Damper type

Multi-blade damper.

Material

Aluminium.

Filters

Panel air filters.
Bag air filters.

Humidifiers

Evaporative humidifiers.

Pre-heaters

-

Manufacturer guidance

Consult manufacturer and insert requirements.

Re-heaters

-

Manufacturer guidance

Consult manufacturer and insert requirements.

Cooling coils

DX cooling coil.
Not required.

Heat recovery

-

Heat recovery equipment

Rotary heat wheel.
Counterflow hexagonal recuperator.
Crossflow plate heat recuperator.

Fans

-

Fan type

Plug fans.

Guidance for specification option:

Direct drive plug fan set.

Attenuators

Rectangular attenuators.

Access

-

Access type

Fully removable panels.

Opening device

Ergonomic handles.

Components requiring access

-

Manufacturer guidance

Consult manufacturer and insert requirements.

Direction of airflow

-

Manufacturer guidance

Consult manufacturer and insert requirements.

Accessories

Internal light.

Sustainability data

Country of product manufacture

United Kingdom

Manufacturing plant location

Material

Steel
Aluminium

Recyclability

Envirotec are registered under the WEEE regulation.
Most parts of the unit can be recycled by normal waste streams.

Expected Life

Ten year

Literature

ENVIROPAC Air Handling Unit (AHU)

ENVIROPAC Air Handling Unit (AHU)