AQX 1
Air handling units.
The AQX range is developed on 32 standard sizes with air flow from 1300 to 100 000 m³/h. All model configurations are available for indoor or outdoor, vertical or horizontal installation as well as with units on top of each other, behind each other, or next to each other.
Features and benefits:
Color | Cream |
Finish | Galvanized Powder-coated |
Material | Steel Stainless steel Aluminium Copper |
Shape | Rectangle |
Length | Bespoke |
Width | Bespoke |
Height | Bespoke |
Warranty description | One year |
Uniclass | |
CAWS | U90/413 Ventilation fan units U90/140 Mechanical supply ventilation |
SKU Code | AQX |
Classification data | |
Standard | To BS EN 13053. |
Duty | |
Air volume | |
Supply | 1490 m³/s. |
Extract | Manufacturer guidanceInsert requirements or omit. |
External resistance | Manufacturer guidanceConsult manufacturer for details and insert requirements. |
Discharge velocity | Manufacturer guidanceConsult manufacturer for details and insert requirements. |
Sound power level | Manufacturer guidanceConsult manufacturer for details and insert requirements. |
Environment | External. Internal. |
Casing construction | |
Standard | To BS EN 1886. |
Casing class | D1. Guidance for specification option: PU50: double skin polyurethane panel, 50 mm thick. RW50: double skin mineral rock wool panel, 50 mm thick. |
Leakage class of casing | L1. Guidance for specification option: PU50: double skin polyurethane panel, 50 mm thick. L2. Guidance for specification option: RW50: double skin mineral rock wool panel, 50 mm thick. |
Filter bypass leakage | To BS EN 1886, section 7. |
Thermal performance of casing | |
Thermal transmittance | T2. Guidance for specification option: PU50: double skin polyurethane panel, 50 mm thick. T3. Guidance for specification option: RW50: double skin mineral rock wool panel, 50 mm thick. |
Thermal bridging | TB3. Guidance for specification option: PU50: double skin polyurethane panel, 50 mm thick. RW50: double skin mineral rock wool panel, 50 mm thick. |
Acoustic insulation of casing | To BS EN 1886, section 9. |
Mechanical safety | To BS EN 1886, section 11. |
Material | Manufacturer's standard. |
Finish | Manufacturer's standard. |
Method of support | Galvanized sheet steel base frame. |
Components | |
Dampers | |
Purpose | Manufacturer guidanceInsert requirements or omit. |
Filters | Prefilters. Soft bags. Rigid bags. HEPA filters. Active absorber carbon. Manufacturer guidanceG2 to HEPA H14 according to CEN-EN 779 and 1822. Consult manufacturer for details. |
Humidifiers | Not required. Steam humidifier. Electrode boiler steam humidifier. Water to waste evaporating wet-deck humidifier. |
Heaters | |
Pre-heaters | Copper coils. Aluminium coils. Manufacturer guidanceAvailable in different diameters, thickness, and four types of tubes geometry. Consult manufacturer for details and insert requirements. |
Re-heaters | Copper coils. Aluminium coils. Manufacturer guidanceAvailable in different diameters, thickness, and four types of tubes geometry. Consult manufacturer for details and insert requirements. |
Cooling coils | Copper cooling coils. Aluminium cooling coils. |
Heat recovery | |
Heat recovery equipment | Cross-flow. Heat wheel, sensible type. Heat wheel, enthalpy/ hygroscopic type Run-around coils. |
Heat recovery class | Manufacturer guidanceConsult manufacturer for details. |
Supply fan | |
Fan type | Forward curved blade. Backwards curved blade. Backwards curved aerofoil blade. Plug fan. |
Average air velocity class | Manufacturer guidanceConsult manufacturer for details and insert requirements. |
Power input class | Manufacturer guidanceConsult manufacturer for details and insert requirements. |
Extract fan | |
Fan type | Manufacturer guidanceInsert requirements or omit. |
Average air velocity class | Manufacturer guidanceInsert requirements or omit. |
Power input class | Manufacturer guidanceInsert requirements or omit. |
Attenuators | Not required. Sound attenuator. |
Accessories | Not required. Weatherproof roof and control protection technical compartment. Weatherproof covers on the external air inlets and outlets. Safety device for moving components. Spotlights and viewing panel for inspection. Inverters on the fan motors. Doors for inspection and service. Other. Guidance for specification option: Other accessories available on request. Consult manufacturer for details and insert requirements. |
Panels | Sandwich-type double-sheet panels with injected polyurethane - PU50. Sandwich-type double-sheet panels with injected mineral wool - RW50. |
Width | 770 mm. Manufacturer guidanceUnit width. |
Height | 570 mm. Manufacturer guidanceUnit height without base. Standard base = 120 mm. |
Air flow | 414 l/s. |
Material | Steel Stainless steel Aluminium Copper |