NBS Source
I'm a manufacturer

Bespoke AOV Smoke Vents SHEV

Verified by manufacturer 2 months ago

Surespan

Aluminium smoke ventilators in aluminium or glass available in a range of bespoke sizes up to 3000 x 1800 mm, all thermally broken and insulated.

Jump to:
BOS
+44 (0)1922 711185 Website

Application

Smoke ventilation, automatic opening vent, smoke window, NSHEV, smoke and heat exhaust ventilator, AOV, smoke vent

Description

Thermally broken 140° AOV smoke ventilators operated by a 24 V d.c. actuator which can be offset and concealed. The lid is filled with 50 mm of CFC and HCFC free insulation which offers a U-value of 0.43 W/m²K. Can also be used for roof access.


Features and benefits:

  • The lid is filled with 50 mm of CFC and HCFC free insulation which offers a U-value of 0.43 W/m²K.
  • The product can also be used for roof access.
  • Supported by heavy-duty stainless steel axel pins.


Range:


- SRHEAOV – Single leaf smoke ventilator:

  • The electromagnetic lock operates via a switch, fire alarm or building management system.
  • A mains supplied control box with 24 V d.c. transformer, battery back-up system is available.


- SRHE/ AOVC – Hidden Mechanism Smoke Ventilator:

  • Electric actuator concealed and hidden from below.
  • Ideal combined with glazed lid.


- SRHGE/AOV – Glazed Smoke Ventilator:

  • Double glazed thermally broken AOV. Can be combined with concealed actuator.

General information

Color

Other

Guidance for specification option:

Natural

Finish

Powder-coated

Mill

Material

Aluminium

Shape

Square

Rectangle

Length

Bespoke

Width

Bespoke

Height

300 mm

Warranty description

Ten year

Uniclass

Ss_65_40_80_80 Smoke and heat exhaust ventilation systemsPrimary

CAWS

L10/490 Roof ventilators

L20/630 Hatches

Product range

Roofing

Specification data - Smoke and heat exhaust ventilation systems

Accessories

Not required.

Concealed actuator.

Offset mechanism.

Guidance for specification option:

Roof access.

Wind deflectors.

Guidance for specification option:

Improved airflow.

Controls

-

Control panel

Break glass.

Fireman's switch.

Key switch.

Push button.

Rain and wind sensor.

Smoke detector.

Type

Glazed top smoke vent.

Solid top smoke vent.

Guidance for specification option:

As standard.

Insulation

50 mm HCFC and CFC free polyisocyanurate – U-value of 0.43 W/m²K.

Curb

300 mm in height as standard.

Performance

All of the standard 140° AOV ventilators are manufactured to meet the requirements of Building Regulations, Approved Document B, BS 9999 and EN 12101-2 and are supplied CE marked.

Standard

CE Marked to EN 12101-2 and compliant to Approved Document B, BS 9999.

Enclosure material

Aluminium with thermally broken lid, frame and upstand.

Sustainability data

Contains Red List materials

No

Country of material origin

United Kingdom

Country of product manufacture

United Kingdom

Material

Aluminium

Recyclability

-

Manufacturer guidance

Surespan manufacture aluminium access products using materials supplied to us from principal aluminium extrusion and plate producers.

We understand that the materials are such that this can use up to 80% of post consumer recycled aluminium content.

Recycled content

As defined in clause 7.8 of BS EN ISO 14021

80 %

BIM objects

BOS

NBS BIM Object Standard

This BIM object has been authored to meet the requirements of the NBS BIM Object Standard.

Find out more about the NBS BIM Object Standard.

Platform Compatible Version
Revit

Revit 2016

4

IFC

IFC2X3

3

Literature

Smoke Vents

Smoke Vents

SRHE-AOV 3000 x 1200 PDF Drawing

SRHE-AOV 3000 x 1200 PDF Drawing

SRHE-AOV 1050 x 1050 PDF Drawing

SRHE-AOV 1050 x 1050 PDF Drawing

Surespan SRHE-AOV Smoke Vent PDF Datasheet

Surespan SRHE-AOV Smoke Vent PDF Datasheet

Case studies

Sliding Glazed Roof Hatches - Great Portland Street, London

Sliding Glazed Roof Hatches - Great Portland Street, London

Glazed AOV Smoke Vent - London

Glazed AOV Smoke Vent - London

Exi-Vent - Bespoke Roof Access and AOV - London

Exi-Vent - Bespoke Roof Access and AOV - London

AOV for Smoke and Fire Safety

AOV for Smoke and Fire Safety