Verified by manufacturer 6 months ago
CADB/T-HE D PRO-REG
QA Certificate
Certificate type
BRE Certificate
Certificate type
Configurable high-efficiency heat recovery units.
Commercial premises, offices, restaurants, public buildings, schools.
Compact heat recovery unit with high-efficiency (up to 93%) counter-flow heat exchanger EUROVENT certified. The casing is made from plasticised galvanized steel in white. Panels are double skinned with thermo-acoustic flameproof insulation (A1/M0), made from 25 mm thick fiberglass in false ceiling versions (Models 04 to 33) and 47 mm in outdoor versions (Models 45 to 100).
Configurable and airtight supply and exhaust spigots, suitable for horizontal and vertical installation. Minimum outdoor temperature -10ºC. For lower temperatures it is necessary to use preheating batteries located in the outdoor air inlet.
Offers a robust construction, versatile assembly, easy maintenance and condensate tray (models 04-33 PRO REG).
Consult technical literature for performance values including airflow, connections, efficiency (>85%), fan speed and unit weight etc.
Versions available:
Horizontal and vertical configurations, without additional heat, electric battery included and water coil included units.
Single phase (CADB-HE PRO-REG) and three phase models (CADT-HE PRO-REG). Airflows from 450 to 10 000 m³/ hour.
- CADB/T-HE D PRO-REG
Heat recovery units without additional incorporated heater.
- CADB/T-HE DC PRO-REG
Heat recovery units with built-in hot water coil. The 3-Way valve is provided as an accessory (see accessories table for this series).
- CADB/T-HE DI PRO-REG
Heat recovery units with built-in electric heater battery.
Motors:
Models 04 to 33: Single phase EC motors with integrated electronic protection, 230V/I/50-60Hz IP44, Class B. Models 45 to 100: Three phase EC motors with integrated electronic protection, 400V/III/50-60Hz IP 54 class B.
Fans:
Plug-fan with backward curved impeller.
Filters:
It is possible to complement the heat recovery unit with a specific range of water and direct expansion coils. Also available, the exclusive module IAQ with a high efficiency in the retention of pollutants associated with outdoor pollution (gases and particulate matter), providing adequate quality to the supplied air, even in polluted outdoor environments.
Control:
It includes an integral operation control, from factory assembled and wired to all the components included in the unit (fans, by-pass, filter pressure switches, temperature probes, etc.). Allows fans control in manual or automatic mode with the display of supply and extract real air volume in all the operation modes (fans pressure transmitters included): Variable airflow (VAV), constant pressure (COP) or constant airflow (CAV) (Available accessories for each mode). Also allows the management of heating coils (DI and DC versions). Integrated air and water temperature probes.
Description of the fan control modes which can be configured:
Finish | Galvanized |
Material | Steel |
Length | Manufacturer guidanceDependent on model specified. |
Width | Manufacturer guidanceDependent on model specified. |
Height | Manufacturer guidanceDependent on model specified. |
Warranty description | Two year |
Uniclass |
Casing construction | |
Fire protection | Category A. |
Material | Galvanized sheet steel. |
Finish | Galvanized. |
Components | |
Filters | Low pressure F7 filters (ePM1 70%).Guidance for specification option: Air supply. M5 filters (ePM10 50%).Guidance for specification option: Air extraction. It is possible to mount a second filter inside the system (supplied as an accessory). G4 pre-filter.F9 filters. |
Heaters | |
Pre-heaters | D: Standard range (Without additional incorporated heater). |
Supply fan | |
Fan type | Plug fans |
Control | Control Plug & Play PRO-REG included. |
Dimensions | 1520 x 760 x 375 mm. Guidance for specification option: Model 04 LH/RH 1750 x 910 x 425 mm. Guidance for specification option: Model 08 LH/RH 1700 x 1050 x 425 mm. Guidance for specification option: Model 12 LH/RH 1950 x 1240 x 450 mm. Guidance for specification option: Model 16 LH/RH 2300 x 1640 x 550 mm. Guidance for specification option: Model 21 and 27 LH/RH |
Power supply | CADB/T-HE: Three-phase power supply. |
Size: | 04. 08. 12. 16. 21. |
Configuration | LH: Left horizontal. LV: Left vertical. RH: Right horizontal. RV: Right vertical. |
Accessories | FB-IAQ HE. Guidance for specification option: Module for air purification, specific for areas with high environmental pollution. IAQ modul with a high efficiency in the retention of pollutants associated with outdoor pollution (gases and particulate matter), providing adequate quality to the supplied aire, even in polluted outdoor environments. Especially suitable for integration in ventilation installations of buildings located in urban or industrial areas with high environmental pollution. FB-CA HE. Guidance for specification option: Odour removal module. Filter module, composed by an activated carbon section and a final filter F9 class. Indicated to protect the ventilation system against the entry of bad odors from outdoor air. It can also be mounted on the extract air. FBL-HE. Guidance for specification option: Outdoor filter module. Filter modules, supplied without filter, to mount filters AFR-HE (capacity for two filters). BA-AF HE. Guidance for specification option: Cold water coil module External cold water coil module, can also be used for hot water (Reversible coil). BA-AFC HE. Guidance for specification option: Double coil module (cold water and hot water) External module that includes a cold water coil and a hot water coil, suitable to be combined with 4 tube-systems. |