Verified by manufacturer over a year ago
Multi circuit, multi application, distributed control and monitoring system for electrical heat tracing, with integrated energy efficient controller and circuit protection.
For electrical heat tracing, with integrated energy efficient controller and circuit protection.
The Raychem ACS-30 system provides electronic control and monitoring for multi-circuit heat tracing applications, including pipe frost protection, surface snow melting, hot water temperature maintenance, gutter and roof de-icing, temperature flow maintenance, and electrical underfloor heating. The Raychem ACS-30 can control up to 260 heat tracing circuits of any application, from a single user interface, allowing building owners and facilities managers to monitor and manage their Building's heat tracing systems from a single point.
Power and control modules (PCMs) can be positioned throughout the building in accordance with the building system requirements. Multiple PCMs can be connected together providing a complete view of the buildings heat tracing systems.
ACS-30-EU-UIT2 User Interface Terminal (UIT):
User interface module for the ACS-30 control and monitoring system, for control and monitoring up to 260 heating cable circuits. Up to 52 PCMs may be connected to each UIT.
ACS-30-EU-PCM2 Power and control module [PCM]:
Power control module for ACS-30, to provide distributed power connection, control and monitoring of heating cable circuits. At least one PCM must be included.
Six versions available as standard:
The PCM module also provides:
ACS-30-EU-MONI-RMM2-E:
Remote monitoring module (RMM) for the ACS-30 control and monitoring system, to measure additional temperatures for control and monitoring of heating cable circuits. Up to 16 RMMs may be controlled by a single UIT, with up to 8 RTDs per RMM.
ACS-30-EU-EMDR-10-MOD:
ACS-30-EU-VIA-DU-20-MOD:
Protonode-RER-10K:
The Raychem ProtoNode is an external, high performance multi-protocol gateway for users needing protocol translation between Building Management Systems (BMS) using BACnetR or MetasysR N2 and the Raychem ACS-30 or TTSIM controllers.
Electrical connection:
Uniclass | |
CAWS | S90/565 Trace heating tape for pipelines |
Operating voltage | 230 V a.c./ 50 Hz. |
Type | ACS-30 System. Guidance for specification option: A multi-circuit, distributed digital control system for single or multiple applications. A centralized control system with distributed power and control modules, complete with user interface terminal (UIT) for central programming; power connection modules (PCM) to provide distributed power, circuit protection, control and monitoring, and remote monitoring modules (RMM) for additional temperature measurement and various energy-saving programmable controllers. ACS-30-EU-EMDR-10-MOD. Guidance for specification option: Provides smart sensor input for roof and gutter de-icing applications. ACS-30-EU-MONI-RMM2-E. Guidance for specification option: Remote monitoring module for the ACS-30 control and monitoring system, to measure additional temperatures for control and monitoring of heating cable circuits. Up to 16 RMMs may be controlled by a single UIT, with up to 8 RTDs per RMM. ACS-30-EU-PCM2. Guidance for specification option: Power control module for ACS-30, to provide distributed power connection, control and monitoring of heating cable circuits. At least one PCM must be included. ACS-30-EU-UIT2. Guidance for specification option: User interface module for the ACS-30 control and monitoring system. For control and monitoring up to 260 heating cable circuits. Up to 52 PCMs may be connected in series to each UIT. |