Circular EIS fire damper with a fire resistance of 30, 60 or 90 minutes depending on the installation type, both for motorized and non-motorized applications. (Previously known as FD and FSD/ MFSD).
Circular EIS fire damper with a fire resistance of 30, 60 or 90 minutes depending on the installation type, both for motorized and non-motorized applications.
(Previously known as FD and FSD/ MFSD.)
CR60 certified installations and sealing methods:
CR60 fields of application:
CR60 building applications:
Circular EIS fire damper with a fire resistance of 30, 60 or 90 minutes depending on the installation type, both for motorized and non-motorized applications.
(Previously known as FD and FSD/ MFSD.)
Features and benefits:
CR60 user benefits:
CR60 range:
Notes:
Relevant links:
Color | White Silver |
Finish | Galvanized Guidance for specification option: Standard body (casing) (steel). Epoxy Guidance for specification option: Inner body & blade.
|
Material | Steel Guidance for specification option: Casing. |
Shape | Circle |
Length | 345 mm Guidance for specification option: Standard models. 500 mm Guidance for specification option: L500 models. |
Width | 100 mm 125 mm 150 mm Guidance for specification option: Not available for CR60-1S models. 160 mm 180 mm Guidance for specification option: Not available for CR60-1S models. Manufacturer guidanceDiameter. |
Height | 100 mm 125 mm 150 mm Guidance for specification option: Not available for CR60-1S models. 160 mm 180 mm Guidance for specification option: Not available for CR60-1S models. Manufacturer guidanceDiameter. |
Warranty description | One year |
Uniclass | |
CAWS | U90/443 Dampers, fire/ smoke |
Classification data | |
Standard | |
Fire dampers | To EN 15650:2010. |
Test methods | To EN 1366-2. Guidance for specification option: Up to 500 Pa. |
Classification | To EN 13501-3. Guidance for specification option: Up to EI90 dependent upon installation requirements; consult manufacturer and insert details. |
Third-party certification | CE marked BCCA-0749-CPR-BC1-606-0464-15650.02-2517. UKCA marked 2822-UKCA-CPR-0055. NF537 marked 18.16. VKF/ AEAI certificate 26815. Hy hygiene certificate W-336769-20-Zd. RISE certificate SC0648-15. |
Arrangement | Single-blade. |
Material | Galvanized steel. Guidance for specification option: Tunnel casing. Consult manufacturer for details of other components. |
Accessories | Inspection opening in tunnel body. Limit switch (open/ closed). Guidance for specification option: To suit specified thermal release mechanism. Not required. |
Thermal release mechanism | Actuator - ONE T 24 V. Actuator - ONE T 230 V. Actuator - ONE-X 24 V. Guidance for specification option: Motor with an integrated control module, used in combination with the ZENiX controls solution by Rf-Technologies. Actuator - ONE-X 230 V. Guidance for specification option: Motor with an integrated control module, used in combination with the ZENiX controls solution by Rf-Technologies. Actuator - Belimo 24 V. Actuator - Belimo 230 V. Fusible link mechanism. |
Actuation temperature | 72°C. |
Dimensions | 100 mm diameter, 345 mm long. 125 mm diameter, 345 mm long. 150 mm diameter, 345 mm long. 160 mm diameter, 345 mm long. 180 mm diameter, 345 mm long. 200 mm diameter, 345 mm long. 250 mm diameter, 345 mm long. 300 mm diameter, 345 mm long. 315 mm diameter, 345 mm long. |
Pressure loss | Guidance for specification option: Insert requirements, dependent on required damper size and air flow/ air speed; consult manufacturer's technical literature for details. |
Air tightness | Class C. Guidance for specification option: To EN 1751. |
Country of product manufacture | Belgium |
Material | Steel Guidance for specification option: Casing. |
Platform | Compatible | Version |
---|---|---|
![]() | - | 1 |
CR120 - Circular EIS Fire Damper (max Ø 315mm) - Fire Damper
CR2 - Circular EIS Fire Damper (max Ø 630mm) - Fire Damper
CR60-1S - "ZERO liabilities" - EIS Circular Fire Damper (max Ø 315mm) - Fire Damper
CU-LT - Rectangular EIS Fire Damper (max W800 x H600 mm) - Fire Damper
CU2 - Rectangular EIS Fire Damper (max W1500 x H1000 mm) - Fire Damper
CU2/B - Large Rectangular EIS Fire Damper - Maximum Four Individual Fire Dampers
CU4 - Rectangular EIS 4Hours Fire Damper - Fire Damper
MARKAGE FD - Large, single unit fire damper - Unique solution for large ducts in combo with space/ depth constraints - Fire Damper