Verified by manufacturer 11 months ago
Standard frame, hidden mullions
Modular ventilation louvres offering excellent airflow and a degree of rain defence, offered with a choice of visible or hidden mullions. Classified as D 1 up to 3.5 m/s.
Ventilation louvres providing excellent airflow and a degree of rain defence.
Modular ventilation louvres offering excellent airflow and a degree of rain defence. Classified as D 1 up to 3.5 m/s.
Features and benefits:
Color | Silver Other |
Finish | Mill Anodized Powder-coated |
Material | Aluminium |
Length | 102 mm Guidance for specification option: Unit depth for standard frame option with visible mullions. Hidden mullions configuration increases overall system depth to 150 mm. Glazing frame option is 108 mm deep. |
Width | Bespoke |
Height | Bespoke |
Uniclass | |
CAWS | L10/54 Louvres H11/140 Louvres L10/650 Metal louvres |
Product range |
Size (l x w x d) | Manufacturer guidanceInsert length and width requirements or insert As drawing or As schedule. Combine units to suit any requirements. Unit depth: 102 mm; overall depth including hidden mullions: 150 mm. |
Material | Extruded 6063-T6 aluminium alloy frame and louvre blades (nominal minimum thickness to be: 1.6 mm for blades, 2.05 mm for heads/cills/jambs & mullions). |
Finish | Milled.Anodized, clear.Anodized, colour.Guidance for specification option: Insert colour requirements. Polyester powder-coated finish, matt, colour.Guidance for specification option: Insert colour requirements. Standard for polyester powder-coated finishes. 30 gloss units. Polyester powder-coated finish, gloss, colour.Guidance for specification option: Insert colour requirements. 70 gloss units. |
Colour | As Finish. |
Construction | Supplied as modules, mechanically assembled in the factory using stainless steel fasteners. Multiple module installations to include hidden mullions. |
Weather performance | |
Water penetration class (minimum) | To BS EN 13030, class D up to 3.5 m/s. |
Discharge loss coefficient (minimum) | To BS EN 13030, class 1: Airflow coefficient Ce (entry): 0.400; Cd (discharge): 0.434.Guidance for specification option: K factor (entry/ discharge): 6.250/ 5.309. |
Louvre configuration | |
Number of banks | One. |
Blade orientation | Horizontal. |
Blade pitch | 75 mm. |
Blade angle | 40°. |
Accessories | None.Bird/ vermin guard, galvanized steel welded mesh.Guidance for specification option: Standard bird/ vermin guard. Pre-fitted welded aluminium frame included. Stainless steel mesh available on request. As guards of any type create additional resistance to airflow and reduce flow rate, louvre sizes should be adjusted to allow for this. Bird/ vermin guard, expanded aluminium welded mesh.Guidance for specification option: Mill finish as standard, can be powder-coated in RAL colours to match louvre. Pre-fitted welded aluminium frame included. As guards of any type create additional resistance to airflow and reduce flow rate, louvre sizes should be adjusted to allow for this. Insect mesh, PVC-coated fibreglass.Guidance for specification option: As standard; stainless steel mesh available on request. As guards of any type create additional resistance to airflow and reduce flow rate, louvre sizes should be adjusted to allow for this. Louvred door(s).Guidance for specification option: Insert requirements.
Dampers, high-performance PVC-U, volume control.Guidance for specification option: Insert requirements.
Dampers, aluminium, volume control.Guidance for specification option: Insert requirements.
|
Cill pan | Required. Guidance for specification option: Insert requirements; size to suit project requirements. Not required. |
Blanking panels | Not required. Single-skin aluminium panels, to match louvre. Guidance for specification option: 2 mm-thick aluminium as standard. Single-skin aluminium panels, mill finish. Guidance for specification option: 2 mm-thick aluminium as standard. Single-skin aluminium panels, other colour/ finish. Guidance for specification option: 2 mm-thick aluminium as standard. Specify colour/ finish required. Insulated panels incorporating A1-classified non-combustible stone wool core. Guidance for specification option: Insulation core material faced on both sides with a 1 mm-thick aluminium sheet and set within an aluminium channel frame. Supplied in sizes to match louvre sizes. Can be pre-fitted to modules if required. |
Material | Aluminium |