Continuous line ventilation louvres offering excellent airflow and a degree of rain defence. Classified as D 1 up to 3.5 m/s.
Ventilation louvres providing excellent airflow and a degree of rain defence.
Continuous line ventilation louvres offering excellent airflow and a degree of rain defence. Classified as D 1 up to 3.5 m/s.
Features and benefits:
Color | Silver Other |
Finish | Mill Anodized Powder-coated |
Material | Aluminium |
Length | 128 mm Guidance for specification option: Unit depth. |
Width | Bespoke |
Height | Bespoke |
Uniclass | |
CAWS | L10/54 Louvres H11/140 Louvres L10/650 Metal louvres |
Product range |
Size (l x w x d) | Manufacturer guidanceInsert requirements or insert As drawing or As schedule and include references as required. Louvre depth (inc. blades and mullions): 128 mm. Stock lengths of blades and mullions will be used to fill in an opening as required. |
Material | All components to be one-piece members extruded from aluminium alloy 6063-T6 (nominal minimum thickness to be: 1.6 mm for blades, 3.18 mm for mullions). |
Finish | Milled.Anodized, clear.Anodized, colour.Guidance for specification option: Insert colour requirements. Polyester powder-coated finish, matt, colour.Guidance for specification option: Insert colour requirements. Standard for polyester powder-coated finishes. 30 gloss units. Polyester powder-coated finish, gloss, colour.Guidance for specification option: Insert colour requirements. 70 gloss units. |
Colour | As Finish. |
Construction | Blades fit into hidden mullions positioned at maximum 1200 mm centres and at joints between blade lengths (based on 1.5 kPa wind load). |
Weather performance | |
Water penetration class (minimum) | To BS EN 13030, class D up to 3.5 m/s. |
Discharge loss coefficient (minimum) | To BS EN 13030, class 1: Airflow coefficient Ce (entry): 0.400; Cd (discharge): 0.434.Guidance for specification option: K factor (entry/ discharge): 6.250/ 5.309. |
Louvre configuration | |
Number of banks | One. |
Blade orientation | Horizontal. |
Blade pitch | 75 mm. |
Blade angle | 40°. |
Accessories | None.Bird/ vermin guard, galvanized steel welded mesh.Guidance for specification option: Standard bird/ vermin guard. Pre-fitted welded aluminium frame included. Stainless steel mesh available on request. As guards of any type create additional resistance to airflow and reduce flow rate, louvre sizes should be adjusted to allow for this. Bird/ vermin guard, expanded aluminium welded mesh.Guidance for specification option: Mill finish as standard, can be powder-coated in RAL colours to match louvre. Pre-fitted welded aluminium frame included. As guards of any type create additional resistance to airflow and reduce flow rate, louvre sizes should be adjusted to allow for this. Insect mesh, PVC-coated fibreglass.Guidance for specification option: As standard; stainless steel mesh available on request. As guards of any type create additional resistance to airflow and reduce flow rate, louvre sizes should be adjusted to allow for this. Louvred door(s).Guidance for specification option: Insert requirements.
Dampers, high-performance PVC-U, volume control.Guidance for specification option: Insert requirements.
Dampers, aluminium, volume control.Guidance for specification option: Insert requirements.
|
Blanking panels | Not required. Single-skin aluminium panels, to match louvre. Guidance for specification option: 2 mm-thick aluminium as standard. Single-skin aluminium panels, mill finish. Guidance for specification option: 2 mm-thick aluminium as standard. Single-skin aluminium panels, other colour/ finish. Guidance for specification option: 2 mm-thick aluminium as standard. Specify colour/ finish required. Insulated panels incorporating A1-classified non-combustible stone wool core. Guidance for specification option: Insulation core material faced on both sides with a 1 mm-thick aluminium sheet and set within an aluminium channel frame. Supplied in sizes to match louvre sizes. Can be pre-fitted to modules if required. |
Perimeter flashing | Required. Guidance for specification option: Cill pan, head and side flashings available. Insert requirements; size to suit project requirements. Not required. |
Material | Aluminium |
CS Louvres - Architectural Line Louvres - Double-Bank Architectural Louvres
CS Louvres - Screening Louvres - Visual Screening Louvres
CS Louvres Rain Defence Louvre B-7505 - Class A Rain Defence Louvres
CS Louvres Rain Defence Louvre PL-5700 - Class A Rain Defence Louvres
CS Louvres Rain Defence Louvre RS-5605 - Class A Rain Defence Louvres
CS Louvres Rain Defence Louvre RS-5900 - Class A Rain Defence Louvres
CS Louvres Rain Defence Louvre RSH-5700AL - Class A Rain Defence Louvres
CS Louvres Rain Defence Louvre RSV-5700 - Class A Rain Defence Louvres
CS Louvres Ventilation Louvre A-3105 - Modular Ventilation Louvres
CS Louvres Ventilation Louvre A-4085 - Modular Ventilation Louvres