Verified by manufacturer 11 months ago
Glazing frame
High-performance louvres with horizontal blades and visible mullions, offering great protection against wind-driven rain penetration and good airflow. Classified as Class A 3 up to 3.0 m/s.
Rain defence louvres for applications requiring good airflow and efficient protection against wind-driven rain ingress.
High performance louvres with horizontal blades and visible mullions, offering great protection against wind-driven rain penetration and good airflow. Classified as A 3 up to 3.0 m/s.
Features and benefits:
Color | Silver Other |
Finish | Mill Anodized Powder-coated |
Material | Aluminium |
Length | 129 mm Guidance for specification option: Unit depth, standard section on elevation only. For glazed facades, unit depth is 133 mm. |
Width | Bespoke Manufacturer guidanceMaximum module width: 3600 mm (based on 1.5 kPa wind load). For manual handling purposes max 80kg / unit is recommended. |
Height | Bespoke Manufacturer guidanceMaximum module height: 3600 mm (based on 1.5 kPa wind load). For manual handling purposes max 80kg / unit is recommended. |
Uniclass | |
CAWS | H11/140 Louvres L10/650 Metal louvres L10/54 Louvres |
Product range |
Size (l x w x d) | Manufacturer guidanceInsert length and width requirements or insert As drawing or As schedule. Unit depth: 133 mm. Combine units to suit any requirements. 25 mm captured glazing frame. Spacers can be used to suit wider glazing sockets. |
Material | All components to be one-piece members extruded from aluminium alloy 6063-T6 (nominal thickness of heads, cills, jambs and mullions to be minimum 1.91 mm; blades to be minimum 1.52 mm). |
Finish | Milled.Anodized, clear.Anodized, colour.Guidance for specification option: Insert colour requirements. Polyester powder-coated finish, matt, colour.Guidance for specification option: Insert colour requirements. Standard for polyester powder-coated finishes. 30 gloss units. Polyester powder-coated finish, gloss, colour.Guidance for specification option: Insert colour requirements. 70 gloss units. |
Colour | As Finish. |
Construction | Supplied as modules, mechanically assembled in the factory using stainless steel fasteners, and complete with a 25 mm glazing frame, suitable for fitting into glazing sockets or use in Structural Silicone Glazing (SSG) system. |
Weather performance | |
Water penetration class (minimum) | To BS EN 13030, class A up to 3.0 m/s.Guidance for specification option: Class B at 3.5 m/s. |
Discharge loss coefficient (minimum) | To BS EN 13030, class 3: Airflow coefficient Ce (entry): 0.289; Cd (discharge): 0.284.Guidance for specification option: K factor (entry/ discharge): 11.973/ 12.398. |
Louvre configuration | |
Number of banks | One. |
Blade orientation | Horizontal. |
Blade pitch | 51 mm. |
Blade angle | Complex extruded blade profile. |
Accessories | None.Bird/ vermin guard, galvanized steel welded mesh.Guidance for specification option: Standard bird/ vermin guard. Pre-fitted welded aluminium frame included. Stainless steel mesh available on request. As guards of any type create additional resistance to airflow and reduce flow rate, louvre sizes should be adjusted to allow for this. Bird/ vermin guard, expanded aluminium welded mesh.Guidance for specification option: Mill finish as standard, can be powder-coated in RAL colours to match louvre. Pre-fitted welded aluminium frame included. As guards of any type create additional resistance to airflow and reduce flow rate, louvre sizes should be adjusted to allow for this. Insect mesh, PVC-coated fibreglass.Guidance for specification option: As standard; stainless steel mesh available on request. As guards of any type create additional resistance to airflow and reduce flow rate, louvre sizes should be adjusted to allow for this. Louvred door(s).Guidance for specification option: Insert requirements.
Dampers, high-performance PVC-U, volume control.Guidance for specification option: Insert requirements.
Dampers, aluminium, volume control.Guidance for specification option: Insert requirements.
Snap-on cover plate to close-off louvre frame.Guidance for specification option: Used to close-off captured glazing frame. Insert requirements. |
Blanking panels | Not required. Single-skin aluminium panels, to match louvre. Guidance for specification option: 2 mm-thick aluminium as standard. Single-skin aluminium panels, mill finish. Guidance for specification option: 2 mm-thick aluminium as standard. Single-skin aluminium panels, other colour/ finish. Guidance for specification option: 2 mm-thick aluminium as standard. Specify colour/ finish required. Insulated panels incorporating A1-classified non-combustible stone wool core. Guidance for specification option: Insert required U-value if known. Insulation core material faced on both sides with a 1 mm-thick aluminium sheet and set within an aluminium channel frame. Supplied in sizes to match louvre sizes. Can be pre-fitted to modules if required. |
Burglar resistance | Required (To EN 1627–1630, RC2). Not required. |
Blast resistance | Required. Guidance for specification option: Can withstand up to 86.87 kPa blast pressure at an impulse of 536.41 kPa/m²·ms. Not required. |
NBS BIM Object Standard
This BIM object has been authored to meet the requirements of the NBS BIM Object Standard.
Find out more about the NBS BIM Object Standard.
Platform | Compatible | Version |
---|---|---|
- | 1 | |
- | 1 |