NBS Source
I'm a manufacturer
Compare variants

CU-LT - Rectangular EIS Fire Damper (max W800 x H600 mm) - Fire Damper

Verified by manufacturer 1 month ago

CU-LT L500 fire damper

Rf-Technologies Variant:
Third party certifications:
  • Classification report acc. to EN 13501-3

    Certificate type

  • UK Conformity Assessed (UKCA)

    UK Conformity Assessed (UKCA)

    Certificate type

  • DoP

    DoP

    Certificate type

  • Hygiene requirements to VDI 6022

    Certificate type

Rectangular EIS fire damper with a fire resistance of 30, 60, 90 or 120 minutes depending on the installation type, for motorized and non-motorized applications. (previously known as FD or FSD / MFSD)

Jump to:
+44 7939316006 Website

Application

Rectangular EIS fire damper with a fire resistance of 30, 60, 90 or 120 minutes depending on the installation type, for motorized and non-motorized applications.

(previously known as FD or FSD / MFSD)


CU-LT Certified installations and sealing methods

  • In wall & floor:
  • rigid wall & floor.
  • flexible wall.
  • asymmetrical flexible wall (shaft wall).
  • Remote of wall.
  • For full details: CU-LT D.o.P. (associated content).


CU-LT Fields of application

  • Passive fire protection.
  • Ventilation systems.


CU-LT Building applications

  • Industrial, commercial & residential buildings.
  • Hospitals and care houses.
  • Data centers and battery plants.
  • Detention institutes.
  • Universities, colleges and schools.

Description

Rectangular EIS fire damper with a fire resistance of 30, 60, 90 or 120 minutes depending on the installation type, for motorized and non-motorized applications.

(previously known as FD or FSD / MFSD)


CU-LT Distinct Product Features (incl. specifications)

  • CE certified against EN 1366-2 and EN 15650.
  • UKCA certified.
  • i <-> o certified.
  • Air-tightness class C against EN 1751.
  • Up to 500 Pa pressure level (standard 300 Pa).
  • Hygiene certified.
  • Swedish BVD and SundaHus rating in place.
  • Minimal distance certified against EN 1366-2.
  • Single, thin insulated damper blade.
  • No mechanics inside the damper body.
  • Fusible link aligned with the open damper blade.
  • 72°C fusible link temperature threshold.
  • Support lugs aligned to DW145 guidance.
  • Designed for use with Belimo motor range (24/ 230 V).
  • Designed for use with ONE motor range (24/ 230 V).
  • Designed for use with ONE-X and ZENiX.
  • Note for clarification:
  • ONE is a motor by Rf-Technologies.
  • ONE-X is motor with an integrated control module, used in combination with the ZENiX controls solution by Rf-Technologies.


CU-LT user benefits:

  • Minimal impact on building space requirements thanks to the minimal distance CE certification and the compact damper and mechanics design
  • down to 25/50 mm vs. structure (floor/ceiling/adjacent wall) or 50 mm between dampers (instead of 75/200 mm standard CE).
  • Minimal pressure loss in the damper body and ventilation system
  • ultimately leading to lower system investments and energy consumption.
  • Minimal acoustic / noise impact.
  • Lowest standby power consumption in the market when using the ONE motor.
  • Easy installation and maintenance (compared to traditional UK type fire dampers).


CU-LT range:

  • Width x Height (mm) 200 x 100 to 800 x 600.
  • Tunnel casing (mm) 300 or 500.


CU-LT configurations & options:

  • Inspection opening on the damper body to allow access to the internal components of the fire damper (option UL).
  • Pre-mounted installation kit for easy installation in flexible wall (option IFW).
  • Circular connection flange with rubber sealing ring (option PRJ) (supersedes the default rectangular connection flange PG20).


Notes:

  • For information about the different types of installation and sealing methods please consult the CU-LT Product application field and/or the CU-LT Declaration of Performance (DoP) and technical documentation.

General information

Color

Silver

White

Finish

Galvanized

Guidance for specification option:

Casing (steel).

Epoxy

Material

Steel

Guidance for specification option:

Casing.

Shape

Rectangle

Square

Length

300 mm

Guidance for specification option:

Casing depth, standard CU-LT model.

500 mm

Guidance for specification option:

Casing depth, CU-LT-L500 model.

Width

200 mm

250 mm

300 mm

350 mm

400 mm

Show more

Height

100 mm

150 mm

200 mm

250 mm

300 mm

Show more

Warranty description

One year

Uniclass

Pr_65_65_24_29 Fire and smoke dampersPrimary

CAWS

U90/443 Dampers, fire/ smoke

Specification data - Fire and smoke dampers

Standard

-

Fire dampers

To EN 15650:2010.

Test

To EN 1366-2.

Classification

To EN 13501-3.

Arrangement

Single-blade.

Classification

Guidance for specification option:

To EN 13501-3, up to EI 120 (ve ho i <-> o) S - (500 Pa) depending on installation method; consult manufacturer and insert details.

Material

Galvanized steel.

Guidance for specification option:

Tunnel casing.

Consult manufacturer for details of other components.

Accessories

IFW CU-LT pre-mounted installation kit for flexible wall.

UL inspection shutter.

Guidance for specification option:

Set of two.

PRJ circular connection.

Guidance for specification option:

Circular connection flange with rubber sealing ring.

Note: This supersedes the PG20 connection.

Limit switch (open/closed).

Guidance for specification option:

Available for fusible links only (see Thermal release mechanism).

Additional limit switch (open/closed).

Guidance for specification option:

Second limit switch, available for actuators only (see Thermal release mechanism).

None.

Fusible links

-

Fusing temperature

72°C.

Dimensions

Guidance for specification option:

Consult manufacturer's literature for performance details including pressure loss, and insert requirements:

  • Nominal height: 100–600 mm in 50 mm increments.
  • Nominal width: 200–800 mm in 50 mm increments.

Standard unit weight between 3.2 and 19.2 kg; consult manufacturer's literature for details.


Intermediate dimensions available on request.

Pressure loss

Guidance for specification option:

Insert details, dependent on required damper size and air flow/air speed; consult manufacturer's technical literature for details.

Air tightness

Class C.

Thermal release mechanism

Actuator - ONE T 24 V.

Guidance for specification option:

Single limit switch included as standard; See Accessories if an additional switch is required.

Actuator - ONE T 230 V.

Guidance for specification option:

Single limit switch included as standard; See Accessories if an additional switch is required.

Actuator - ONE-X 24 V.

Guidance for specification option:

Motor with an integrated control module, used in combination with the ZENiX controls solution by Rf-Technologies.

Actuator - ONE-X 230 V.

Guidance for specification option:

Motor with an integrated control module, used in combination with the ZENiX controls solution by Rf-Technologies.

Actuator - Belimo 24 V.

Guidance for specification option:

Single limit switch included as standard; See Accessories if an additional switch is required.

Show more

Integral accessories

Tunnel casing extension.
PG20 connection to ducts with 20 mm flanges.
Inspection opening(s).

Guidance for specification option:

Tunnel casing extension:

  • Extension at the wall side to facilitate the connection to the duct when the supporting construction is thicker than 100 mm.
  • This variant also ensures that the damper blade doesn’t exceed the casing at the wall side (up to a height of 550 mm), which allows to connect a grill or a bend directly on the damper flange or to use a circular connection.


PG20 connection to ducts with 20 mm flanges:

  • Connection either with sliding profile or with bolts. 
  • Elliptical holes: Ø9.5 x 16 mm.


Inspection opening(s):

  • Standard opening (all models).
  • Inspection opening for a cable camera (endoscope): Only applicable where ONE or ONE-X actuator is specified.

Third-party certification

CE marked BCCA-0749-CPR-BC1-606-0464-15650.05-0464.
UKCA marked 2822-UKCA-CPR-0060.
NF537 marked 18.19.
VKF/ AEAI certificate 26812.
Hy hygiene certificate W-379334-23-Zd.
RISE certificate SC0644-15.

Sustainability data

Country of material origin

Europe

Country of product manufacture

Belgium

Material

Steel

Guidance for specification option:

Casing.

BIM objects

Platform Compatible Version
Revit
-

1

Third party certifications

Classification report acc. to EN 13501-3

Classification report acc. to EN 13501-3

CU-LT Classification Report Warringtonfire

UK Conformity Assessed (UKCA)

UK Conformity Assessed (UKCA)

CU-LT UKCA Certificate

DoP

DoP

CU-LT Declaration of Performance

Classification report acc. to EN 13501-3

Classification report acc. to EN 13501-3

CU-LT Classification Report Efectis

Hygiene requirements to VDI 6022

Hygiene requirements to VDI 6022

CU-LT Hygiene Certificate

Literature

CU-LT Technical Product Documentation

CU-LT Technical Product Documentation

CU-LT DW145 compliant installation guide - rigid wall

CU-LT DW145 compliant installation guide - rigid wall

CU-LT DW145 compliant installation guide - plasterboard wall

CU-LT DW145 compliant installation guide - plasterboard wall

CU-LT DW145 compliant installation guide - floor/ceiling

CU-LT DW145 compliant installation guide - floor/ceiling