Verified by manufacturer 15 days ago
D901 DN20
A flow measurement device.
A flow measurement device.
D901 Flow Measurement Device is suitable for systems where pipes have been sized on the basis that pipe frictional losses lie in the range 100 to 400 Pa/m.
D902 Flow Measurement Device (1/2"/15 mm size only) is suitable for the measurement of ultra-low flows in the range 0.015 to 0.06 L/sec e.g. flows to fan coil units.
Features and benefits:
Standard | To BS 7350: 1990, BS EN 10226, BS EN 1254/2, BS EN 12165 and BS EN 12164. |
Material | DZR copper alloy. |
Connections | Pressure-tight joints threaded to BS EN 10226-1 and compression to BS EN 1254-2. |
Inlets/outlets diameter | 20 mm. |
Dimensions | 58 x 61 mm. |
Weight | 0.3 kg. |
Approvals | Water Regulations Advisory Scheme (WRAS). |
PressureRange | Temperature (Threaded): -10 to +100°C: 25 bar, Temperature (Threaded): +110°C: 23.4 bar, Temperature (Threaded): +120°C: 21.8 bar. Temperature (Compression): -10 to +30°C: 16 bar, Temperature (Compression): +65°C: 10 bar, Temperature (Compression):+120°C: 5 bar. Maximum temperature 120°C. WRAS Approved Product to 99°C. |
Flow capacity | 6.1 Kv and 4.7 Kvs. Guidance for specification option: Headloss (K): 9.1. |
Material | Brass |
Recyclability | Recyclable Guidance for specification option: Recycle locally, consult manufacturer for details. |
Expected Life | 20 year |