Verified by manufacturer 20 days ago
4 Series C - PHEX Size 3
ISO 9001 Quality Management
Certificate type
Range of cooling interface units supplying indirect cooling.
Suitable for domestic and commercial applications.
Danfoss Cooling Interface Units (CIUs) for indirect cooling enabling the primary circuit to be kept hydraulically separate. These are supplied with fully insulated and vapour sealed enclosures, designed to prevent condensation of the internal valves and pipes. Insulated enclosures means that the Danfoss CIU components can be left uncovered, which makes access for maintenance tasks considerably easier.
All Danfoss CIUs are supplied with the Danfoss Electronic Controller (ECL). The ECL's are intelligent temperature regulators for heat networks and communal heating. By means of weather compensation and application keys, they can be adapted to a variety of project specific requirements, ensuring a high level of comfort and optimum energy utilisation.
Features and benefits:
Color | Grey |
Finish | Galvanized |
Material | Steel Polypropylene |
Shape | Rectangle |
Length | 450 mm 322 mm |
Width | 686 mm 594 mm |
Height | 970 mm 708 mm |
Warranty description | Two year |
Uniclass | |
CAWS | T90/110 Heating system |
Duty | |
Primary flow temperature | 8/14℃. |
Primary return temperature | 11.7℃. |
Pressure drop | 30 kPa. |
Flow rate | 7.2 L/min. |
Heating supply temperature | 6℃.Manufacturer guidanceCooling Network Supply. |
Casing | Anthracite grey expanded polypropylene. |
Insulation | Full EPP insulation.Guidance for specification option: Thermal conductivity: 0.038–0.040 W/(m2 *K). |
Components | |
Primary | Space heating heat exchanger. |
Secondary | Isolating valve. |
Controls | Danfoss - AVQM.Guidance for specification option: Pressure independent control valve with adjustable flow limiter. |
Capacity | 3 kW. |
Dimensions | 708 x 594 x 322 mm. Manufacturer guidanceH x W x D. |
Pressure | Nominal pressure: PN 16. |
Country of product manufacture | Denmark |
Material | Steel Polypropylene |
Manufacturing plant location | |
Expected Life | 20 year |
RavenResidential Ironworks, Mill Road Case Study
Quayside Extra Care, Totnes - FlatStation Case Story
Pressure Independent Thermostatic Radiator Valves Case Study
Middlewood Locks - FlatStation Case Story
District Heat-as-a-Service
Agar Grove Camden - Heat Interface Unit Case Story
Case Story Greenside Views, Mitcham, London