NBS Source
I'm a manufacturer
Compare variants

Danfoss FlatStation 7 Series - Heat Interface Unit

Verified by manufacturer 5 months ago

7 Series DS FI - DHW PHEX Size 1-x

SAV Systems Variant:
Third party certifications:
  • EPD

    EPD

    Certificate type

Range of heat interface units supplying instantaneous domestic hot water and indirect heating.

Jump to:
+44 01483 771 910 Website

Application

Suitable for domestic and commercial applications.

Description

Range of heat interface units supplying instantaneous domestic hot water and indirect heating.


Features and benefits:

  • BESA registered.
  • Wide capacity range.
  • Primed domestic hot water control with 8°C set back (FI, R-FI, IV).
  • Integral differential pressure control.
  • Pressure absorber.
  • 20-year operating life.
  • Self-acting mechanical control.
  • Copper braised stainless steel Micro Plate™ Heat Exchanger.
  • Stainless steel pipes.
  • Fully insulated (FI, R-FI, IV).
  • Instantaneous shut off of heat network supply water through PHEX after tapping (reduces scaling of heat exchanger).
  • Strainers on heat network supply, heating return and cold water pipes.

General information

Color

White

Grey

Finish

Lacquered

Material

Steel

Polypropylene

Shape

Rectangle

Length

235 mm

270 mm

385 mm

430 mm

Width

528 mm

530 mm

540 mm

Height

690 mm

710 mm

800 mm

Warranty description

Three year

Uniclass

Pr_60_60_38_36 Heat interface unitsPrimary

CAWS

S90/230 Instantaneous hot water supply

S90/130 Instantaneous hot water supply

T90/110 Heating system

Specification data - Heat interface units

Duty

-

Primary flow temperature

60℃.

Primary return temperature

16.8–20.0℃.

Pressure drop

45 kPa.

Flow rate

12.6–15.6 L/min.

Heating supply temperature

RAD: 50/30°C.
UFH: 35/30°C.

Hot water supply temperature

45℃.

50℃.

Casing

White lacquered steel cover.

Insulation

Full EPP insulation.

Manufacturer guidance

Thermal conductivity: 0.038–0.040 W/(m²*K).

Components

-

Primary

Domestic hot water heat exchanger.

Secondary

Isolating valve.

Controls

DHW - IHPT self-acting mechanical controller.
Heating - AVPL self-acting mechanical controller.

Capacity

35.0–38.0 kW.

Dimensions

800 x 540 x 430 mm.

Manufacturer guidance

H x W x D.

Pressure

Nominal pressure: PN 10.
Min. DCW static pressure: pmin = 1 bar.
Max. differential pressure: ∆pmax = 4.5 bar.

Plate heat exchanger

HTG PHEX Size: x-2 RAD.

Guidance for specification option:

  • HTG circuit: 50/30℃.
  • HTG capacity: 5.0 kW.
  • Space HTG flow rate: 217 L/h.
  • Heat network return: 33.0℃.
  • Pressure pump head: 20 kPa.

HTG PHEX Size: x-3 RAD.

Guidance for specification option:

  • HTG circuit: 50/30℃.
  • HTG capacity: 6.5 kW.
  • Space HTG flow rate: 282 L/h.
  • Heat network return: 32.8℃.
  • Pressure pump head: 20 kPa.


HTG PHEX Size: x-4 RAD.

Guidance for specification option:

  • HTG circuit: 50/30℃.
  • HTG capacity: 11.0 kW.
  • Space HTG flow rate: 477 L/h.
  • Heat network return: 32.6℃.
  • Pressure pump head: 20 kPa.

HTG PHEX Size: x-5 RAD.

Guidance for specification option:

  • HTG circuit: 50/30℃.
  • HTG capacity: 18.0 kW.
  • Space HTG flow rate: 781 L/h.
  • Heat network return: 32.4℃.
  • Pressure pump head: 20 kPa.

HTG PHEX Size: x-1 UFH.

Guidance for specification option:

  • HTG circuit: 35/30℃.
  • HTG capacity: 2.0 kW.
  • Space HTG flow rate: 346 L/h.
  • Heat network return: 30.1℃.
  • Pressure pump head: 25 kPa.

Show more

Sustainability data

Country of product manufacture

Denmark

Material

Steel

Polypropylene

Manufacturing plant location

Embodied carbon

A1-A3 (production stage) as defined in BS EN 15804

80.1 kg CO₂ eq/unit

Third party certifications

Third party certifications

EPD

EPD

MD-22107-EN

Literature

Danfoss FlatStation 7 Series DS FI

Danfoss FlatStation 7 Series DS FI

Danfoss FlatStation 7 Series DS R-FI

Danfoss FlatStation 7 Series DS R-FI

Danfoss FlatStation 7 Series BS

Danfoss FlatStation 7 Series BS

Danfoss FlatStation 7 Series DS IV

Danfoss FlatStation 7 Series DS IV