Verified by manufacturer 11 days ago
EcoActive 100 HRU
Heat recovery systems.
Suitable for education and residential applications.
Situated within a high-level void or exposed, giving winter and summer ventilation and also summer night time purging to each room. These units can also be externally roof mounted.
Each unit contains a heat exchanger with a minimum efficiency of 74%, giving a minimum supply air temperature of 17°C. Units also have low energy EC supply and extract fans handling volumes up to 1.0 m3/s.
Each unit is controlled via a CO2/ temperature room sensor and intelligent controller to give the correct ventilation at all times.
Features and benefits:
Color | Silver Other |
Finish | Galvanized Powder-coated |
Material | Steel Aluminium |
Shape | Rectangle |
Length | 1450 mm 1800 mm 2200 mm 2450 mm |
Width | 1000 mm 1200 mm 1350 mm 1550 mm 1850 mm |
Height | 330 mm 450 mm 520 mm 560 mm 610 mm |
Uniclass |
Standard | To BS EN 13053. |
Duty | |
Air volume | |
Supply | 0.1 m³/s. |
Extract | 0.1 m³/s. |
External resistance | 250 Pa. |
Sound power level | 61 dB.Guidance for specification option: Consult manufacturer for details. |
Environment | External.Internal. |
Casing construction | |
Material | Galvanized sheet steel. |
Finish | Self-finish.Polyester powder-coated.Guidance for specification option: Available in standard colours from BS 4800 or RAL ranges. Insert requirements. |
Method of support | Suspended with M10 threaded rod either fixed through the pre-drilled holes within the corner sections or welded lugs. |
Components | |
Dampers | |
Purpose | Bypass damper.Guidance for specification option:
|
Filters | G4 panel air filters. |
Heaters | |
Pre-heaters | Guidance for specification option: Heating coil options are available, consult manufacturer for details. |
Re-heaters | Guidance for specification option: Heating coil options are available, consult manufacturer for details. |
Cooling coils | Guidance for specification option: Cooling coil options are available, consult manufacturer for details. |
Heat recovery | |
Heat recovery equipment | Plate heat exchanger - ERI Corporation PCF-I-3-95-280-T-BR-110-B-SM-HO. |
Supply fan | |
Fan type | Centrifugal fans - GR20V-4IP.Z8.VR.Guidance for specification option:
|
Extract fan | |
Fan type | Centrifugal fans - GR20V-4IP.Z8.VR.Guidance for specification option:
|
Attenuators | Not required.EcoActive 100.Guidance for specification option: 615 x 300 x 200 mm (L x W x H). EcoActive 200.Guidance for specification option: 615 x 400 x 300 mm (L x W x H). EcoActive 300.Guidance for specification option: 615 x 400 x 350 mm (L x W x H). EcoActive 400.Guidance for specification option: 750 x 500 x 400 mm (L x W x H). |
Accessories | Not required.Room sensor - CO₂ and temperature.Guidance for specification option: Wall mounted and wired back to unit. Speed control.Guidance for specification option: 0–10 V signal. |
Integral accessories | Access panel, side (removable panels on quarter turn cam locks and plastic handles). |
Leakage | To EN 16798-3. Manufacturer guidanceLeakage class. |
Building Management System (BMS) connection | Modbus. |
Flow rate | 60 L/s. 100 L/s. Manufacturer guidanceFor ventilation of spaces with occupancies of up to 12 people (based on 8/l/s/p). |
Support frame | Extruded aluminium to BS 1474 - 30 x 30 mm pentapost box section. |
Mullions | Extruded aluminium to BS 1474 – 30 mm mullion joint. |
Controls | Siemens Climatix Controllers, interface units, wall-mounted sensors and room operator units. Guidance for specification option: Consult manufacturer's literature for details and options. |
Dimensions | 1450 x 1000 x 330 mm. |
Unit weight | 134 kg. |
Country of product manufacture | United Kingdom |