NBS Source
I'm a manufacturer

EX II 2 GD Dust Approved and Increased Safety (EExemd) Resettable Manual Alarm Callpoint

Verified by manufacturer 3 months ago

Johnson Controls

ATEX approved resettable manual alarm callpoint.

Jump to:
BOS
Website

Application

Suitable for special hazard areas (ATEX approved). Suitable for use in zones 1 and 2.

Description

An EX II 2 GD dust approved and increased safety (EExemd) resettable manual alarm callpoint for use with the EExd Flameproof MIM800 input module in EExd housing on an Addressable Detection and Releasing System in gas and dust explosive risks. Only compatible with Consys Version 17.0 and above when used with 577.800.067.


Features and benefits:

  • GRP enclosure, light, strong and not subject to corrosion
  • Resettable element
  • Explosion protection (ATEX approved)
  • In line and end of line resistors
  • Red epoxy finish
  • Seven terminals
  • Lift flap for extra protection against inadvertent operation
  • One changeover switch
  • Captive cover screws
  • Key operated test facility
  • M20 bottom cable entry.


General information

Color

Red

Finish

Painted

Material

Glass Reinforced Plastic (GRP)

Shape

Rectangle

Length

75 mm

Guidance for specification option:

Depth

Width

120 mm

Height

126 mm

Warranty description

Three year

Uniclass

Pr_75_80_30_50 Manual call pointsPrimary

CAWS

W90/336 Manual call points

Specification data - Manual call points

Standard

To EN 50019, EN 50018, EN 50028. CENELEC EN 50014.

Third-party certification

ATEX approved EX II 2 GD, EEemdIICT4, BAS02ATEX2105X.

Integral red visual indicator

Required.

Environmental category

Indoor.

Mounting

Surface.

Power source

Up to 250 V.

Operating temperature

–20 to +50°C.

Ingress protection

IP66/67.

Sustainability data

Contains Red List materials

No

Country of material origin

Czechia

Country of product manufacture

Czechia

Material

Glass Reinforced Plastic (GRP)

Manufacturing plant location

Expected Life

Ten year

BIM objects

BOS

NBS BIM Object Standard

This BIM object has been authored to meet the requirements of the NBS BIM Object Standard.

Find out more about the NBS BIM Object Standard.

Platform Compatible Version
Revit
-

1

Literature

514.001.107 EX II 2 GD Dust Approved Resettable Manual Alarm Callpoint

514.001.107 EX II 2 GD Dust Approved Resettable Manual Alarm Callpoint