NBS Source
I'm a manufacturer
Compare variants

FDMR 60 - Circular EIS Fire Damper (Ø100-400mm) - Manual/Motorised - Fire Damper

Verified by manufacturer 12 days ago

Design .01 - Manual control and thermal

Mandik UK Limited Variant:
Third party certifications:
  • Hygiene requirements to VDI 6022

    Certificate type

  • DoP

    DoP

    Certificate type

  • Certificate of constancy of performance

    Certificate type

  • EPD

    EPD

    Certificate type

A manual or motorised fire damper for air conditioning ducts.

Jump to:
0117 4526376 Website

Application

The fire dampers are suitable for installation in arbitrary position in vertical and horizontal passages of fire separating constructions. The fire damper can be installed into:

  • Solid wall construction made e.g. of normal concrete/ masonry or porous concrete with a minimum thickness of 100 mm.
  • Gypsum wall construction with a minimum thickness of 100 mm.
  • Solid ceiling construction made e.g. of normal concrete or porous concrete with minimum thickness according to BS EN 1366-2.

Additional applications may be available, please reference product Technical Specifications for more detail.

Description

A Fire Damper is used to prevent fire and reduce smoke spreading from one compartment to another through the air ductwork system which may penetrate fire separating walls and floors

Features and benefits:

  • CE certified to EN 15650.
  • Tested in accordance with EN 1366-2.
  • Classified to EN 13501-3+A1.
  • Corrosion resistant to EN 15650.

General information

Color

Silver

Finish

Galvanized

Material

Steel

Shape

Circle

Length

300 mm

500 mm

Width

100 mm

125 mm

140 mm

150 mm

160 mm

Show more

Height

100 mm

125 mm

140 mm

150 mm

160 mm

Show more

Warranty description

Two year

Uniclass

Pr_65_65_24_29 Fire and smoke dampersPrimary

CAWS

U90/443 Dampers, fire/ smoke

Specification data - Fire and smoke dampers

Standard

-

Fire dampers

To EN 15650.

Test

To EN 1366-2.

Classification

To EN 13501-3.

Aerodynamic performance

To BS 1751.

Guidance for specification option:

Damper body: Class C; Damper blade: Class 3.

Arrangement

Single-blade.

Classification

EIS60.

Manufacturer guidance

Refer to the manufacturer's literature for placement and installation details to achieve the fire resistance value.

Material

Zinc-coated steel.

Fusible links

-

Fusing temperature

72°C.

Guidance for specification option:

As standard.

104°C.

147°C.

Spare fusible links

-

Manufacturer guidance

Insert requirements or omit.

Design

Spiro damper (SL).

Spiro damper, with installation brackets (SK).

Actuator

Manual.

Diameter

100 mm.

125 mm.

140 mm.

150 mm.

160 mm.

Show more

Length

-

Manufacturer guidance

300–500 mm. Insert requirements or refer to a drawing.

Duct connection

Mandik FFDM breakaway joint.

Guidance for specification option:

FFDM allows a breakaway connection between a duct and fire damper according to DW/145. The FFDM is a flanged breakaway joint with a plastic pad which will melt at 80°C, allowing the duct to break away from the damper and ensure the dampers integrity is maintained.

Refer to FFDM – Technical specifications for options and insert requirements.

Breakaway joint (supplied by others).

Guidance for specification option:

Insert requirements.

Manufacturer guidance

Breakaway joints are a required accessory for the fire dampers. These joints are required on both sides of the damper.

Sustainability data

Country of product manufacture

Czechia

Material

Steel

Third party certifications

BIM objects

Platform Compatible Version
Revit
-

1

Third party certifications

Hygiene requirements to VDI 6022

Hygiene requirements to VDI 6022

Hygienic assessment - Fire dampers

DoP

DoP

FDMR 60 – Declaration of performance

Certificate of constancy of performance

Certificate of constancy of performance

FDMR 60 – Certificate

EPD

EPD

Environmental Product Declaration - Fire Dampers

Literature

FDMR 60 – Technical specifications (142/19)

FDMR 60 – Technical specifications (142/19)

FFDM – Technical specifications (137/19)

FFDM – Technical specifications (137/19)

Similar products from Mandik UK Limited

FDMA - Rectangular EIS Fire Damper (≤1600x1000mm) - Manual/Motorised - Fire Damper

FDMA - Rectangular EIS Fire Damper (≤1600x1000mm) - Manual/Motorised - Fire Damper

FDMB - Rectangular EIS Fire Damper (≤1000x500mm) - Manual/Motorised  - Fire Damper

FDMB - Rectangular EIS Fire Damper (≤1000x500mm) - Manual/Motorised - Fire Damper

FDML - EIS Multi-Blade Motorised Fire Damper (≤1000x1000mm) - Fire Damper

FDML - EIS Multi-Blade Motorised Fire Damper (≤1000x1000mm) - Fire Damper

FDMQ - Rectangular EIS Fire Damper (≤1500x800mm) - Manual/Motorised  - Fire Damper

FDMQ - Rectangular EIS Fire Damper (≤1500x800mm) - Manual/Motorised - Fire Damper

FDMQ 120 - Rectangular EIS Fire Damper (≤1500x800mm) - Manual/Motorised  - Fire Damper

FDMQ 120 - Rectangular EIS Fire Damper (≤1500x800mm) - Manual/Motorised - Fire Damper

FDMQ 180 - Rectangular EIS Fire Damper (≤1500x800mm) - Manual/Motorised  - Fire Damper

FDMQ 180 - Rectangular EIS Fire Damper (≤1500x800mm) - Manual/Motorised - Fire Damper

FDMR - Circular EIS Fire Damper (Ø100-800mm) - Manual/Motorised - Fire Damper

FDMR - Circular EIS Fire Damper (Ø100-800mm) - Manual/Motorised - Fire Damper

FDMR 180 - Circular EIS Fire Damper (Ø200-800mm) - Manual/Motorised - Fire Damper

FDMR 180 - Circular EIS Fire Damper (Ø200-800mm) - Manual/Motorised - Fire Damper