Verified by manufacturer 22 days ago
DN15: Fig. 2910
Bronze thermal circulation valves, PN16.
Suitable for domestic hot water systems to assist with protection against Legionella.
Bronze thermal circulation valves, PN16.
Features and benefits:
Operation:
Color | Yellow Guidance for specification option: Body. Green Guidance for specification option: Cap. |
Material | Bronze Guidance for specification option: Body. Plastic Guidance for specification option: Protective cap. Nylon Guidance for specification option: Temperature adjusting cap and isolation unit handwheel. Brass Guidance for specification option: Bonnet and associated parts, body seat, plug, bush, stem and stem seat retainer. Stainless steel Guidance for specification option: Thermal unit stem. |
Uniclass | |
CAWS | S90/650 Flow-reducing/ servicing valves S90/650 Flow reducing/ servicing valves S90/630 Double check valve assemblies S90/680 Thermostatic mixing valves S90/680 Thermostatic mixing valves |
Product range |
Material | Body: Bronze CC49IK, Protective cap: Polypropylene, Temperature adjusting cap (TU) and handwheel isolation unit (IU): Nylon 6, Body seat, plug, bush, bonnet and associated parts (TU): DZR brass CW602N, Bonnet, stem and stem seat retainer (IU): DZR brass CW602N, Stem (TU): Stainless steel SS EN 10088-3 – 1.4305, O-ring seals (TU and IU): EPDM rubber, Body seat (IU): PTFE.Guidance for specification option:
Manufacturer guidance
|
Connections | Taper threaded to BS EN 10226-2. |
Third party certification: | WRAS Approved. |
Inlets/outlets diameter | DN15. Manufacturer guidanceNominal. |
Dimensions | 114 x 80 x 37 mm. Manufacturer guidance
|
Weight | 0.76 kg. |
Thread size | 15 mm. Manufacturer guidanceFemale end connections with pipe threaded to EN 10226 Rc. |
FlowClass | Low flow. |
Upper temperature stability | ±2°C. Guidance for specification option: At set temperature. |
Maximum temperature | 90°C. Manufacturer guidance
|
PressureClass | PN16. |
Integral accessories | Isolation valve with thermometer access point and settable temperature sensing cartridge. Manufacturer guidanceFitted with thermal circulation valve assembly. |