Verified by manufacturer 18 days ago
DN100
Ductile iron, Y-type strainer (Fig. 811) and variant (Fig. 911) inclusive of two Fig. 631 test points.
Suitable for saturated steam service.
Ductile iron, Y-type strainer (Fig. 811) and variant (Fig. 911) inclusive of two Fig. 631 test points.
Features and benefits:
Color | Blue Guidance for specification option: Body and cover. |
Material | Cast iron |
Uniclass |
Material | Body, cover and plug: Ductile iron BS EN 1563, Screen: Stainless steel grade 304, Gasket: Teflon/ Graphite.Guidance for specification option: Stainless steel to BS EN SS 304 and AISI 304. |
Mesh size | Single screen, 1.6 mm mesh. |
Connections | |
Type | Flanged to BS EN 1092-2, PN25. |
Size | DN100.Manufacturer guidanceNominal diameter. |
PressureRange | Temperature: -10 to +120°C: 25 bar, +220°C: 21.5 bar. Guidance for specification option:
Manufacturer guidance
|
Dimensions | 352 x 232 x 300 mm. Manufacturer guidanceNominal A x B x C, where C = withdrawal distance for the strainer screen. |
Weight | 32.4 kg. |
Flow capacity | 229 Kv. Manufacturer guidanceFlow coefficient Kv. |
EffectiveArea | 40%. Manufacturer guidanceFree flow area/cm². |
Plug | DN25. Manufacturer guidanceCover plug size. |
Material | Cast iron |
Recyclability | Recycle locally |
Expected Life | 20 year |