Verified by manufacturer over a year ago
Flow maintenance of greasy waste pipes.
For use on all insulated greasy waste pipes exposed to the risk of lower temperature, viscosity-inhibited flow.
An energy-efficient, self-regulating trace heating system for use on all insulated greasy waste pipes exposed to the risk of lower temperature, viscosity-inhibited flow.
The system is complete with low smoke zero-halogen self-regulating heating cables, advanced energy-efficient controller and cold-applied components, CE marked and certified according to IEC (EN) codes.
System components:
Self-regulating heating cables (XL-Trace):
The self-regulating heating cables are tested to and compliant with IEC 61034-2, IEC 60754-1, IEC 62395: 2013, IEC 60068-2-5 and 2-9 (for low smoke emission, zero-halogen, self-extinguishing properties, UV resistance and colour fastness under UV exposure), qualified for a useful lifetime in excess of 25 years, highly flexible with a 10 mm bend radius and suitable for use with 20 A circuit breakers.
The self-regulating heating cables include a conductive polymer core, modified low smoke zero-halogen electrical insulation (radiation cross-linked to ensure long life expectancy), tinned copper braid and modified low smoke zero-halogen over jacket printed with cable model, batch number and metre marks for ease of installation within maximum circuit lengths.
All insulated greasy waste pipework is fitted with self-regulating heating cables 10XL2-ZH (or 15/26/31XL2-ZH on larger pipes) and installed to a maximum circuit length of 215 m at 5°C switch on (or 160, 135 or 118 m for 15/26/31XL2-ZH respectively).
Cold applied interconnection and termination components (Rayclic):
Interconnection and termination are made with cold-applied insulation displacement connectors and gel-type end seals which are UV-resistant, IP68 and 65°C rated, suitable for 2500 V d.c. insulation resistance test, with Torx head fittings and both audible and visual installation confirmation.
Single circuit, single application energy efficient controller:
All greasy waste flow maintenance circuits are controlled with a programmable, energy-efficient line sensing thermostat (RAYSTAT V5).
Multi circuit, single application control panel with integrated energy efficient controller:
All greasy waste flow maintenance circuits are controlled and monitored by an integrated, multi-circuit, electrically protected control panel (SBS-FP-xx), complete with integrated energy efficient controller (Elexant 450c).
Multi circuit, multi-application distributed control and monitoring system with integrated energy efficient controller:
All greasy waste flow maintenance circuits are controlled and monitored using a centralized control system with distributed power and control modules (RAYCHEM ACS-30), complete with integrated energy efficient controller (Elexant 450c ). The centralized control system provides pre-programmed parameters to provide concurrent control for hot water temperature maintenance, pipe freeze protection, flow maintenance, surface snow melting, roof and gutter de-icing and floor heating applications.
Thermal insulation:
Insulation selection and thickness is strictly in accordance with the XL-Trace design guide.
Electrical connection:
Design:
The manufacturer shall be able to provide all design calculations, including heat loss and corresponding selection of heating cables; electrical schedules providing cable lengths, circuit breakers, circuit start up currents, operating currents and loads, line list summary and single line details; system layout and schematic drawings indicating power connections, tees and end seals; controller configuration listing and wiring diagrams.
Installation:
All flow maintenance trace heating cables shall be installed in accordance with the design plans, within the defined maximum circuit lengths, tested and commissioned strictly in accordance with the manufacturer’s instructions (IM-CDE1547) using a 2500 V d.c. megger. Installation of thermal insulation shall be closely coordinated with the responsible sub-contractors. ATE-180 shall be used on plastic pipes.
Warranty description | Two years Guidance for specification option: Warranty of two years for controllers, extended to 6 years when installed by the manufacturer or by a trained installer recognized by them. 12 years Guidance for specification option: Warranty of ten years for heating cables/ connection components, extended to 12 years when installed by the manufacturer or by a trained installer recognized by them. |
Uniclass | |
CAWS | S90/565 Trace heating tape for pipelines |
Application | Greasy waste pipe flow maintenance. |
Heat emitters | 10XL2-ZH.Guidance for specification option: On greasy waste pipes. 15/26XL2-ZH.Guidance for specification option: On larger greasy waste pipes. 31XL2-ZH.Guidance for specification option: On high temperature greasy waste pipes. |
Cold applied, insulation displacement interconnection components and end seals | RayClic-CE-02. Guidance for specification option: Power connection with 1.5 m power cable, gel-filled end seal and support bracket. IP68. RayClic-E-02. Guidance for specification option: Gel-filled end seal. RayClic-PS-02. Guidance for specification option: Powered splice, connection for two cables with 1.5 m power cable. Supplied with two gel-filled end seals and support bracket. IP68. RayClic-PT-02. Guidance for specification option: Power T-connection with 1.5 m power cable for three cable connection. Supplied with three gel-filled end seals and support bracket. IP68. RayClic-S-02. Guidance for specification option: Splice for joining two lengths of heating cable, with one support bracket. IP68. |