NBS Source
I'm a manufacturer
Compare variants

Heat Exchange Module

Verified by manufacturer 5 months ago

HEM Lx 100-12

Powrmatic Ltd Variant:

Gas fired heat exchange modules for a wide variety of air heating and drying applications.

Jump to:
+44 (0)1460 53535 Website

Application

For air heating and drying applications including new and refurbished air handling units, duct heaters and dryers. 

Description

The compact design and flexible configuration of Powrmatic HEMx gas fired heat exchange modules combine to provide designers with efficient and cost effective solutions for a wide variety of air heating and drying applications.


The HEMx range is available in two differing configurations: HEM-Lx 15–200 and HEM-SLx 30–200. Where higher duties are required modules may be installed in either parallel or in series. Depending on model and size such multiple modules may be supplied factory pre-assembled. Fuel usage and emissions are a key consideration within the HEMx design with all modules offering efficiencies compliant with the latest ErP legislation.


Features and benefits:

  • ErP 2021 ready.
  • Reduced NOx levels.
  • Redesigned control panel access.
  • Customisable configuration.
  • Capacity range from 30 kW to 200 kW.
  • Reduced air stratification.
  • Replacement unit matching from other suppliers.
  • Proven durability and long operational life.

General information

Color

Silver

Material

Steel

Stainless steel

Shape

Rectangle

Width

400 mm

530 mm

590 mm

648 mm

800 mm

Show more

Height

458 mm

531 mm

741 mm

601 mm

950 mm

Show more

Warranty description

Two year

Guidance for specification option:

Heat exchanger warranty.

Uniclass

Pr_60_65_37_33 Gas-fired heater batteriesPrimary

CAWS

T90/110 Heating system

T90/110 Heating system

Specification data - Gas-fired heater batteries

Application

External.

Internal.

Duty

-

Minimum airflow

2.77 m³/s.

Air on temperature

35°C.

Air off temperature

70°C.

Gas

-

Type

Natural gas.

Guidance for specification option:

Supplied ready for use with natural gas (G20).

LPG.

Guidance for specification option:

Alternative LPG propane (G31) firing available upon request as a conversion kit.

Consumption

11.63 m³/h (natural gas).

Gas pipe connection size

¾" BSP/Rc (natural gas).

Electrical supply

230 V, 1 ph, 50 Hz.

Flue diameter

130 mm.

Airflow direction

Horizontal.

Guidance for specification option:

Standard airflow.

Vertical.

Guidance for specification option:

Optional airflow for horizontal unit installation.

Unit type

Single.

Heat exchanger tube material

Aluminized steel tubes.

AISI T-409 stainless steel tubes.

AISI T-316 stainless steel tubes.

Accessories

None.

External enclosure, galvanized.

Plant room enclosure, galvanized.

External enclosure, galvanized and powder-coated BS 10-A-05.

Plant room enclosure, galvanized and powder-coated BS 10-A-05.

External enclosure, galvanized and powder-coated BS/ RAL.

Guidance for specification option:

Other standard BS or RAL colours are available priced upon application. Insert requirements.

Plant room enclosure, galvanized and powder-coated BS/ RAL.

Guidance for specification option:

Other standard BS or RAL colours are available priced upon application. Insert requirements.

Output

33.1–99.3 kW.

Sustainability data

Contains Red List materials

No

Country of product manufacture

United Kingdom

Literature

HEMx Brochure

HEMx Brochure