Verified by manufacturer 3 months ago
WRAS
Certificate type
Electronically controlled Heat Interface Unit. With auto fault diagnosis and prepayment switching. Available with remote monitoring.
Indirect interface for instantaneous DHW and space heating.
HIPER II is an electronically controlled heat interface unit.
The electronics provide automatic fault diagnostics and also error warnings when the supply to the HIU is not suitable for efficient operation. These can be read on the screen, or when linked with the a remote monitoring device, can be read externally. Multiple parameters are adjustable to enable the commissioning engineers to adapt the operation of the HIU to suit the operating conditions of the heat network it is installed in. A temperature controlled keep warm function can be used or turned off if the installation does not require. To protect the pump during long summer periods where heating is not required can be programmed to run the pump for minutes to prevent sticking and formation of chemical residue on moving parts.
Features and benefits:
Color | White |
Finish | Powder-coated |
Material | Steel Polyurethane (PUR) Guidance for specification option: Flexible low density open cell polyether polyurethane foam. |
Shape | Rectangle |
Length | 265 mm |
Width | 465 mm |
Height | 585 mm |
Warranty description | Three year |
Uniclass | |
CAWS | T90/110 Heating system T90/110 Heating system |
Standard | Tested to BESA UK HIU Test regime. |
Duty | |
Primary flow temperature | Manufacturer guidanceConsult manufacturer and insert requirements. |
Primary return temperature | 20–90℃.Guidance for specification option: Factory set: 40℃. |
Pressure drop | Manufacturer guidanceConsult manufacturer and insert requirements. |
Flow rate | 4.5 L/hr.Guidance for specification option: Average flow measured by BESA for 8 hour period of keep warm.
|
Heating supply temperature | Manufacturer guidanceConsult manufacturer and insert requirements. |
Hot water supply temperature | Manufacturer guidanceConsult manufacturer and insert requirements. |
Casing | Steel. |
Insulation | Flexible low density open cell polyether polyurethane foam.Guidance for specification option:
|
Components | |
Primary | Domestic hot water heat exchanger. |
Secondary | Pump. |
Controls | Differential pressure control valve. |
Pressure | DH maximum pressure: 16 bar. |
Inlet pressure | Minimum required inlet pressure for cold water supply: 1.5 bar. Guidance for specification option: Recommended no higher than 3 bar. |
Maximum temperature | HTG maximum temperature: 3 bar. |
Adjustment | HTG - radiators temperature adjustment: 30°C to 75°C. |
Output | HTG maximum output (85°C at 1330 L/hr): 29 kW. |
Heating capacity (minimum) | Heating pump nominal head capacity: 70 kPa. |
Electrical supply | Single phase 230 v, 50 Hz. |
Weight | 25.4 kg. Guidance for specification option: HIU installation weight, no cover. HIU weight - Gross, including packaging: 32.5 kg. |
Dimensions | 585 x 465 x 265 mm. Guidance for specification option: Height x width x depth. |
Contains Red List materials | Yes |
Country of material origin | Italy |
Country of product manufacture | Europe |
Material | Steel Polyurethane (PUR) Guidance for specification option: Flexible low density open cell polyether polyurethane foam. |