NBS Source
I'm a manufacturer

HIPER II Heat Interface Unit (HIU) - HIU

Verified by manufacturer 4 months ago

Intatec Ltd Third party certifications:
  • WRAS

    WRAS

    Certificate type

Electronically controlled Heat Interface Unit. With auto fault diagnosis and prepayment switching. Available with remote monitoring.

Jump to:
+44 (0)1889 272180 Website

Application

Indirect interface for instantaneous DHW and space heating.

Description

HIPER II is an electronically controlled heat interface unit.


The electronics provide automatic fault diagnostics and also error warnings when the supply to the HIU is not suitable for efficient operation. These can be read on the screen, or when linked with the a remote monitoring device, can be read externally. Multiple parameters are adjustable to enable the commissioning engineers to adapt the operation of the HIU to suit the operating conditions of the heat network it is installed in. A temperature controlled keep warm function can be used or turned off if the installation does not require. To protect the pump during long summer periods where heating is not required can be programmed to run the pump for minutes to prevent sticking and formation of chemical residue on moving parts.


Features and benefits:

  • Auto fault diagnostics.
  • Modbus communications to report system conditions or fault conditions to a central monitor or BMS.
  • Pay as you go (prepayment) switching.
  • Integral shut off for pay as you go (PAYG) - no external valve required.
  • Automatic closing of the control valve when power lost for anti-scald and stop unnecessary heat returns.
  • Pump protection against pump sticking.
  • Heating radiators or underfloor (UFH) selection.
  • Optimized or constant temperature heating option.
  • Viewing access to heat meter calculator by lift up panel.
  • Integral flushing and bypass filter valve.
  • Test ports.
  • UFH slab drying cycle.
  • Frost protection function.
  • PWM pump speed control.
  • Pressure differential and flow control by fast acting PICV with stepper actuator.
  • Integral shock arrestor for cold water supply.
  • Three strainers, one for each circuit.
  • Filling group for heating circuit.
  • Start up menu for commissioning
  • Set time and date.
  • Heating flow limitation setting.
  • Programmable return temperature limitation control.
  • Manual pump override (for test).
  • Room thermostat normally OPEN or CLOSED option.
  • Additional switch for adding a second pump to load a cylinder or use as an alarm.
  • Optional programme to add a temperature controlled hot water storage cylinder.
  • Programmable anti-legionella cycle.
  • Keep warm function by temperature and time, programmable or switch off options.
  • Select which plate heat exchanger to use for the keep warm function to limit scale formation.

General information

Color

White

Finish

Powder-coated

Material

Steel

Polyurethane (PUR)

Guidance for specification option:

Flexible low density open cell polyether polyurethane foam.

Shape

Rectangle

Length

265 mm

Width

465 mm

Height

585 mm

Warranty description

Three year

Uniclass

Pr_60_60_38_36 Heat interface unitsPrimary

CAWS

T90/110 Heating system

T90/110 Heating system

Specification data - Heat interface units

Standard

Tested to BESA UK HIU Test regime.

Duty

-

Primary flow temperature

-

Manufacturer guidance

Consult manufacturer and insert requirements.

Primary return temperature

20–90℃.

Guidance for specification option:

Factory set: 40℃.

Pressure drop

-

Manufacturer guidance

Consult manufacturer and insert requirements.

Flow rate

4.5 L/hr.

Guidance for specification option:

Average flow measured by BESA for 8 hour period of keep warm.

  • DHW maximum flow at 1300 L/hr with 80°C DH and ΔT 40°C: 28.5 L/min.
  • DHW maximum flow at 1300 L/hr with 55°C DH and ΔT 40°C: 5.8 L/min.

Heating supply temperature

-

Manufacturer guidance

Consult manufacturer and insert requirements.

Hot water supply temperature

-

Manufacturer guidance

Consult manufacturer and insert requirements.

Casing

Steel.

Insulation

Flexible low density open cell polyether polyurethane foam.

Guidance for specification option:

  • Containing a flame-retardant additive to reduce ease of ignition.
  • Black dual melt 25–30 micron polyurethane film on one surface.
  • Thermal conductivity 0.033 W/mk.
  • Density BS EN 845:1995: 24±3 Kg/m³ .

Components

-

Primary

Domestic hot water heat exchanger.

Secondary

Pump.

Controls

Differential pressure control valve.

Pressure

DH maximum pressure: 16 bar.
DH maximum pressure differential: 4 bar (400 kPa).
HTG maximum pressure / safety valve setting: 3 bar.
HTG safety valve setting: 3 bar.
DHW side maximum pressure: 10 bar.

Inlet pressure

Minimum required inlet pressure for cold water supply: 1.5 bar.

Guidance for specification option:

Recommended no higher than 3 bar.

Maximum temperature

HTG maximum temperature: 3 bar.

Adjustment

HTG - radiators temperature adjustment: 30°C to 75°C.
UFH - underfloor heating temperature adjustment: 20°C to 50°C.
DHW temperature adjustment: 45°C to 65°C.

Output

HTG maximum output (85°C at 1330 L/hr): 29 kW.
HTG minimum output: 1 kW.
DHW maximum output at 1300 L/hr with 80°C DH and ΔT 40°C: 80 kW.
DHW minimum output at 400 L/hr with 55°C DH and ΔT 40°C: 15 kW.

Heating capacity (minimum)

Heating pump nominal head capacity: 70 kPa.

Electrical supply

Single phase 230 v, 50 Hz.

Weight

25.4 kg.

Guidance for specification option:

HIU installation weight, no cover.

HIU weight - Gross, including packaging: 32.5 kg.

Dimensions

585 x 465 x 265 mm.

Guidance for specification option:

Height x width x depth.

Sustainability data

Contains Red List materials

Yes

Country of material origin

Italy

Country of product manufacture

Europe

Material

Steel

Polyurethane (PUR)

Guidance for specification option:

Flexible low density open cell polyether polyurethane foam.

Third party certifications

WRAS

WRAS

WRAS Certificate No. 2012353 - HIPER2TPSZ80 Electronically Controlled Heat Interface Units

Literature

HIPER II Indirect Installation and Operation Manual

HIPER II Indirect Installation and Operation Manual

Heat Interface Unit Technical Information

Heat Interface Unit Technical Information

HIPER II Heat Interface Unit Data Sheet

HIPER II Heat Interface Unit Data Sheet

HIPER II Heat Interface Unit - Direct

HIPER II Heat Interface Unit - Direct

HIPER II Heat Interface Unit - Heating Only

HIPER II Heat Interface Unit - Heating Only

HIPER II Heat Interface Unit - Hot Water Only

HIPER II Heat Interface Unit - Hot Water Only

BESA 2023 Test Regime Report - HIPER II HIU

BESA 2023 Test Regime Report - HIPER II HIU

Case studies

Case Study for HIUs at Morello

Case Study for HIUs at Morello

Kingmaker House

Kingmaker House