Verified by manufacturer 4 days ago
Type 10 Radiator
Independent sustainability assessment
Certificate type
DoP
Certificate type
Wall or floor mounted radiator in steel with fixed casing and convectors.
Suitable choice for the interior of any room.
Hudevad P5 Horizontal has a clean design and reliable output. A 2 mm thick front plate with the characteristic Hudevad edge makes is one of the main features of the P5. The deep models of the P5 Horizontal and all Lowline models have closed sides, welded steel top with a streamlined effect which allows the air to circulate for maximum efficiency.
Features and benefits:
Color | White Guidance for specification option: White RAL 9016 70% Gloss. Other |
Finish | Powder-coated |
Material | Steel |
Shape | Rectangle |
Length | 410 mm 420 mm 510 mm 520 mm 610 mm |
Width | 35 mm 62 mm 102 mm 160 mm |
Height | 320 mm 420 mm 520 mm 620 mm 720 mm |
Warranty description | Ten year |
Uniclass | |
CAWS | T90/465 Radiators T90/465 Radiators |
Standards | To BS EN 442-1 and BS EN 442-2. |
Radiator type | Single plain panel.Guidance for specification option: Type 10. |
Output | Guidance for specification option: Consult manufacturer and insert requirements. |
Finish | Powder-coated.Guidance for specification option: In accordance with DIN 55900, EN 442. |
Connections | Guidance for specification option: Consult manufacturer and insert requirements. Manufacturer guidanceAll connections 1/2” standard (adapters available). |
Accessories | Not required.Feet.Easy clean bracket.Forced water.Danfoss TRV head.Guidance for specification option: For tapping Code 11,12, 13,14,16 and 18. |
Casing | To EN 10051, 2.00 mm steel. |
Heating element | To EN 442, steel panel. |
Colour | White RAL 9016, gloss 70. Guidance for specification option: Standard. Other. Guidance for specification option: Can be painted in other colours. Insert requirements. |
TestPressure | 13 bar. |
Operating pressure (maximum) | To EN 442, 10 bar. |
Operating temperature | 110°C. |
Height | 320 mm. Guidance for specification option: H1: 320 mm. H2: 300 mm. 420 mm. Guidance for specification option: H1: 420 mm. H2: 400 mm. 520 mm. Guidance for specification option: H1: 520 mm. H2: 500 mm. 620 mm. Guidance for specification option: H1: 620 mm. H2: 600 mm. 720 mm. Guidance for specification option: H1: 720 mm. H2: 700 mm. Manufacturer guidanceFor height 200 mm, please see P5 Lowline. |
Depth | 35 mm. |
Length | Guidance for specification option: 410—2020 mm. Consult manufacturer and insert requirements. Manufacturer guidanceAvailability of lengths varies depending of chosen tapping configuration and height. |
Tapping configuration | Tapping code 10. Guidance for specification option: Tapping type: ABCD (4 taps). L1: 410—2010 mm (in 100 mm increments). L2: 200—2000 mm (in 100 mm increments). Tapping code 11. Guidance for specification option: Tapping type: FF built-in valve (6 tap right). L1: 420—2020 mm (in 100 mm increments). L2: 200—2000 mm (in 100 mm increments). Danfoss TRV Head required. Tapping code 13. Guidance for specification option: Tapping type: Center tap, right (8 taps). L1: 420—2020 mm (in 100 mm increments). L2: 200—2000 mm (in 100 mm increments). Danfoss TRV Head required. Tapping code 15. Guidance for specification option: Tapping type: E/F, no valve. L1: 610—2010 mm (in 100 mm increments). L2: 400—1800 mm (in 100 mm increments). Tapping code 16. Guidance for specification option: Tapping type: E/F, with valve Right/Left. L1: 610—2010 mm (in 100 mm increments). L2: 400—1800 mm (in 100 mm increments). Danfoss TRV Head required. Manufacturer guidanceSee manufacturers literature for more information. |
Contains Red List materials | No |
Country of material origin | Europe |
Country of product manufacture | United Kingdom |
Recyclability | Yes |
Recycled contentAs defined in clause 7.8 of BS EN ISO 14021 | 99 % |
Platform | Compatible | Version |
---|---|---|
- | 1 |