Verified by manufacturer 5 days ago
KoolthermDuct-20
ISO 9001 Quality Management
Certificate type
ISO 14001 Environmental Management Systems
Certificate type
ISO 45001 Health and Safety Management
Certificate type
EnMS ISO 50001
Certificate type
ISO 37301 (Compliance Management Systems)
Certificate type
EPD
Certificate type
An energy-efficient rigid insulation for rectangular, circular and flat oval HVAC ductwork.
Suitable for use on rectangular, circular and flat oval ductwork in HVAC or building services applications.
Energy-efficient rigid insulation for rectangular, circular and flat oval HVAC ductwork suitable for new build and refurbishment projects in the residential, commercial, institutional and industrial sectors. Comprised of a fibre-free rigid phenolic insulation core externally faced with an aluminium vapour barrier foil and internally with a glass tissue based facing.
Insulated duct support inserts:
During the installation of galvanised steel ductwork, the contractor should place insulated support inserts between ducts and supports, to extend both sides of the support to allow for tape application. Insulated duct support inserts should be of suitable compressive strength to carry the loads transmitted to the supports and should be of the same thickness as that of the adjacent duct insulation.
Features and benefits:
Color | Pink |
Finish | Smooth Foil |
Material | Phenolic foam |
Length | 1200 mm |
Width | 600 mm 2400 mm |
Height | 20 mm 25 mm 30 mm 35 mm 40 mm |
Uniclass | |
CAWS | U90/490 Site-applied insulation to ductwork U90/490 Site-applied insulation to ductwork U90/425 Rigid ductwork and fittings U90/425 Rigid ductwork and fittings |
Product range |
Standard | To BS EN 14314:2009+A1:2013. |
Form | Duct slab. |
Thermal conductivity | 0.024 W/m K at -20°C.0.022 W/m K at 10°C.0.023 W/m K at 19°C.0.023 W/m K at 25°C.0.026 W/m K at 50°C.0.031 W/m K at 80°C. |
Finish | Exposed aluminium foil facing. |
Fire performance | To BS EN 13501-1, class B-s2, d0 (exposed foil face); class E (non exposed tissue face). |
Insulation thickness (minimum) | 20 mm. |
Vapour barrier | |
Material | Factory-applied aluminium foil.Guidance for specification option: Standard for indoor use. |
Protection | Not required.Waterproof finish.Guidance for specification option: If the ductwork is to the external of the building the insulation must be covered with a waterproof finish. |
Accessories | Not required.Aluminium tape.Guidance for specification option: Insulation is applied to ductwork with high strength aluminium tape. Adhesive.Guidance for specification option: When tape is not sufficient, use adhesive, or mechanical means, or a combination of both. Bands (preferably aluminium).Guidance for specification option: Bands (preferably aluminium) and matching seals are used as additional mechanical means on circular ductwork. |
FM approved | FM Approved per Approval Standard 4924 as a low fire hazard. Guidance for specification option: Kingspan Kooltherm® Duct Insulation is FM Approved per Approval Standard 4924 as a low fire hazard, which does not require automatic sprinkler protection of itself, when manufactured and installed in accordance with the conditions defined by the approval report. |
Compressive strength (minimum) | 100 kPa at 10% compression. |
Closed cell content | ≥90%. |
Nominal density range | 35–40 kg/m³. |
Face Size (length x width) | 600 x 1200 mm. 1200 x 2400 mm. |
Country of material origin | United Kingdom |
Country of product manufacture | United Kingdom |
Material | Phenolic foam |
Embodied carbonA1-A3 (production stage) as defined in BS EN 15804 | 2.77 kg CO₂ eq/kg Guidance for specification option: Per EPD, Kooltherm Duct has an embodied carbon content of 9.14e+0 per functional unit, divided by 3.3 kg/m2 = 2.77 kg CO2 eq per kg. Manufacturer guidance1 m² of Kooltherm Duct insulation at a thickness that gives an R-value of 3.000 m².K/W (66mm) gives a GWP of 9.14 kg CO2 equivalent per functional unit, in Life cycle stages A1 - A3 (Raw material supply, transport and manufacturing). This is equivalent to 2.77 kg CO2e/kg of Kooltherm Duct Insulation |
Recycled contentAs defined in clause 7.8 of BS EN ISO 14021 | 0 % |
NBS BIM Object Standard
This BIM object has been authored to meet the requirements of the NBS BIM Object Standard.
Find out more about the NBS BIM Object Standard.
Platform | Compatible | Version |
---|---|---|
- | 1 | |
- | 1 |
ISO 9001 Quality Management
ISO 9001:2015 - Pembridge
ISO 14001 Environmental Management Systems
ISO 14001:2015 - Pembridge
ISO 45001 Health and Safety Management
ISO 45001:2018 - Pembridge
EnMS ISO 50001
ISO 50001:2018 - Pembridge
ISO 37301 (Compliance Management Systems)
ISO 37301:2021 - Pembridge
EPD
BREG EN EPD No: 000362