NBS Source
I'm a manufacturer
Compare variants

Kingspan Therma Duct Insulation

Verified by manufacturer 2 months ago

Kingspan Therma Duct Insulation - 25 mm

Kingspan Insulation Variant:
Third party certifications:
  • ISO 9001 Quality Management

    Certificate type

  • ISO 45001 Health and Safety Management

    Certificate type

  • ISO 37301 (Compliance Management Systems)

    Certificate type

  • EPD

    EPD

    Certificate type

  • Certificate of Approval

    Certificate of Approval

    Certificate type

An energy-efficient rigid insulation for rectangular, circular and flat oval HVAC ductwork installed outdoors.

Jump to:
BOS
+44 (0)1544 388601 Website

Application

Suitable for use on rectangular, circular and flat oval ductwork installed outdoors in HVAC/ building services applications for both new build and refurbishment projects in the residential, commercial, institutional and industrial sectors.

Description

An energy efficient rigid insulation for rectangular, circular and flat oval HVAC ductwork installed outdoors that is suitable for new build and refurbishment projects in the residential, commercial, institutional and industrial sectors. The insulation has a fibre-free rigid polyisocyanurate (PIR) insulation core, faced on both sides with a protective low vapour-permeability trilaminate foil.

Insulation located outdoors must be protected with a compatible weatherproof material.


Insulated duct support inserts:

During the installation of galvanised steel ductwork, the contractor should place insulated support inserts between ducts and supports, to extend both sides of the support to allow for tape application. Insulated duct support inserts should be of suitable compressive strength to carry the loads transmitted to the supports and should be of the same thickness as that of the adjacent duct insulation.


Standards:

Kingspan Therma™ Duct insulation boards are manufactured to the highest standards under a quality control system certified to:

  • BS EN ISO 9001: 2015 (Quality Management Systems. Requirements).
  • BS EN ISO 14001: 2015 (Environmental Management Systems. Requirements).
  • BS ISO 45001: 2018 (Occupational health and safety management systems) and
  • BS EN ISO 50001: 2018 (Energy Management Systems).


Sustainability:

Manufactured with a CFC / HCFC-free blowing agent that has very low Ozone Depletion Potential (ODP) and low Global Warming Potential GWP < 5

General information

Color

Cream

Material

Polyisocyanurate (PIR)

Guidance for specification option:

Foam.

Shape

Rectangle

Length

1200 mm

Width

600 mm

Height

25 mm

30 mm

40 mm

50 mm

Uniclass

Pr_25_31_28_65 Polyisocyanurate (PIR) foam insulationPrimary

CAWS

U90/490 Site-applied insulation to ductwork

U90/490 Site-applied insulation to ductwork

Product range

Ducting

Specification data - Polyisocyanurate (PIR) foam insulation

Standard

BS EN 14308:2009 + A1:2013.

Fire performance

Class F to BS EN 13501-1.

Protection

The insulation must be covered with a waterproof finish.

Thickness

25 mm.

Compressive Strength (at 10% deformation)

Minimum 120 kPa.

ThermalConductivity

0.022 W/m·K at -20°C.
0.023 W/m·K at 10°C.
0.023 W/m·K at 19°C.
0.024 W/m·K at 25°C.
0.027 W/m·K at 50°C.
0.031 W/m·K at 80°C.

Closed cell content

≥90%.

Nominal density range

30–35 kg/m³.

Sustainability data

Country of material origin

United Kingdom

Country of product manufacture

United Kingdom

Material

Polyisocyanurate (PIR)

Guidance for specification option:

Foam.

Embodied carbon

A1-A3 (production stage) as defined in BS EN 15804

4.61 kg CO₂ eq/kg

Guidance for specification option:

Per EPD, Therma Duct has an embodied carbon content of 9.43e+0 per functional unit, divided by 2.046 kg/m2 = 4.61 kg CO2 eq per kg.

Manufacturer guidance

1 m² of Therma Duct Insulation at a thickness that gives an R-value of 3.000 m².K/W (66mm) gives a GWP of 9.43 kg CO2 equivalent per functional unit, in Life cycle stages A1 - A3 (Raw material supply, transport and manufacturing). This is equivalent to 4.61 kg CO2e/kg of Therma Duct Insulation

Recycled content

As defined in clause 7.8 of BS EN ISO 14021

0 %

Third party certifications

BIM objects

BOS

NBS BIM Object Standard

This BIM object has been authored to meet the requirements of the NBS BIM Object Standard.

Find out more about the NBS BIM Object Standard.

Platform Compatible Version
IFC
-

1

Revit
-

1

Third party certifications

ISO 9001 Quality Management

ISO 9001 Quality Management

ISO 9001:2015 - Pembridge

ISO 45001 Health and Safety Management

ISO 45001 Health and Safety Management

ISO 45001:2018 - Pembridge

ISO 45001 Health and Safety Management

ISO 45001 Health and Safety Management

ISO 45001:2018 - Selby

ISO 9001 Quality Management

ISO 9001 Quality Management

ISO 9001:2015 - Selby

ISO 37301 (Compliance Management Systems)

ISO 37301 (Compliance Management Systems)

ISO 37301:2021 - Pembridge

ISO 37301 (Compliance Management Systems)

ISO 37301 (Compliance Management Systems)

ISO 37301:2021 - Selby

EPD

EPD

BREG EN EPD No: 000322

Certificate of Approval

Certificate of Approval

BES 6001

Literature

Kingspan Therma Duct Insulation - 05/23

Kingspan Therma Duct Insulation - 05/23