Verified by manufacturer 28 days ago
Kingspan Therma Duct Insulation - 25 mm
ISO 9001 Quality Management
Certificate type
ISO 45001 Health and Safety Management
Certificate type
ISO 37301 (Compliance Management Systems)
Certificate type
EPD
Certificate type
An energy-efficient rigid insulation for rectangular, circular and flat oval HVAC ductwork installed outdoors.
Suitable for use on rectangular, circular and flat oval ductwork installed outdoors in HVAC/ building services applications for both new build and refurbishment projects in the residential, commercial, institutional and industrial sectors.
An energy efficient rigid insulation for rectangular, circular and flat oval HVAC ductwork installed outdoors that is suitable for new build and refurbishment projects in the residential, commercial, institutional and industrial sectors. The insulation has a fibre-free rigid polyisocyanurate (PIR) insulation core, faced on both sides with a protective low vapour-permeability trilaminate foil.
Insulation located outdoors must be protected with a compatible weatherproof material.
Insulated duct support inserts:
During the installation of galvanised steel ductwork, the contractor should place insulated support inserts between ducts and supports, to extend both sides of the support to allow for tape application. Insulated duct support inserts should be of suitable compressive strength to carry the loads transmitted to the supports and should be of the same thickness as that of the adjacent duct insulation.
Standards:
Kingspan Therma™ Duct insulation boards are manufactured to the highest standards under a quality control system certified to:
Sustainability:
Manufactured with a CFC / HCFC-free blowing agent that has very low Ozone Depletion Potential (ODP) and low Global Warming Potential GWP < 5
Color | Cream |
Material | Polyisocyanurate (PIR) Guidance for specification option: Foam. |
Shape | Rectangle |
Length | 1200 mm |
Width | 600 mm |
Height | 25 mm 30 mm 40 mm 50 mm |
Uniclass | |
CAWS | U90/490 Site-applied insulation to ductwork U90/490 Site-applied insulation to ductwork |
Product range |
Standard | BS EN 14308:2009 + A1:2013. |
Fire performance | Class F to BS EN 13501-1. |
Protection | The insulation must be covered with a waterproof finish. |
Thickness | 25 mm. |
Compressive Strength (at 10% deformation) | Minimum 120 kPa. |
ThermalConductivity | 0.022 W/m·K at -20°C. |
Closed cell content | ≥90%. |
Nominal density range | 30–35 kg/m³. |
Country of material origin | United Kingdom |
Country of product manufacture | United Kingdom |
Material | Polyisocyanurate (PIR) Guidance for specification option: Foam. |
Embodied carbonA1-A3 (production stage) as defined in BS EN 15804 | 4.61 kg CO₂ eq/kg Guidance for specification option: Per EPD, Therma Duct has an embodied carbon content of 9.43e+0 per functional unit, divided by 2.046 kg/m2 = 4.61 kg CO2 eq per kg. Manufacturer guidance1 m² of Therma Duct Insulation at a thickness that gives an R-value of 3.000 m².K/W (66mm) gives a GWP of 9.43 kg CO2 equivalent per functional unit, in Life cycle stages A1 - A3 (Raw material supply, transport and manufacturing). This is equivalent to 4.61 kg CO2e/kg of Therma Duct Insulation |
Recycled contentAs defined in clause 7.8 of BS EN ISO 14021 | 0 % |
NBS BIM Object Standard
This BIM object has been authored to meet the requirements of the NBS BIM Object Standard.
Find out more about the NBS BIM Object Standard.
Platform | Compatible | Version |
---|---|---|
- | 1 | |
- | 1 |
ISO 9001 Quality Management
ISO 9001:2015 - Pembridge
ISO 45001 Health and Safety Management
ISO 45001:2018 - Pembridge
ISO 45001 Health and Safety Management
ISO 45001:2018 - Selby
ISO 9001 Quality Management
ISO 9001:2015 - Selby
ISO 37301 (Compliance Management Systems)
ISO 37301:2021 - Pembridge
ISO 37301 (Compliance Management Systems)
ISO 37301:2021 - Selby
EPD