Verified by manufacturer 7 months ago
Magnelis
Double leaf, inward or outward opening flood doorset with certified security protection to LPS 1175 SR2.
Doors are tailored to individual requirements. They are particularly popular among utility clients, and companies operating within remote or substation sites.
Double leaf, inward or outward opening flood doorset.
Certified by the LPCB to LPS 1175: Issue 7 Security Rating 2. To achieve SR2 accreditation, doors are attacked using tools with a high mechanical advantage, such as a hand drill, junior hacksaw and a claw hammer.
Features and benefits:
Color | Beige Black Blue Bronze Brown |
Finish | Gloss Matt Powder-coated Semi-gloss Textured |
Material | Steel Guidance for specification option: Zintec, stainless steel, or Magnelis. Stainless steel Zintec steel |
Shape | Rectangle |
Width | Bespoke |
Height | Bespoke |
Uniclass | |
CAWS | L20/480 Doorsets L20/55 Doorsets |
Configuration | Double leaf, single action, inward opening.Double leaf, single action, outward opening. |
Doorset size | Guidance for specification option: Insert requirement:
|
Performance | |
Fire resistance | |
Integrity | Not required.240 minutes (FD240).Guidance for specification option: Available with a fire rating up to FD240, providing integrity fire resistance for up to 240 minutes, certified by Exova under the CERTIFIRE scheme (certificate number CF5107). Note:
|
Acoustic performance | Not required.Required.Guidance for specification option: Insert requirements. Sound reduction to BS EN ISO 10140-2 available, consult manufacturer for details. |
Intruder resistance | |
Minimum requirement | To LPS 1175, SR 2.Guidance for specification option: M2M2 doors are LPCB certified to LPS 1175: Issue 7 Security Rating 2 (certificate number 312f). |
Conformity | Certification by accredited third-party certification body. |
Frame | |
Material | Magnelis.Manufacturer guidance1.5 mm thick. |
Threshold | Steel.Aluminium. |
Finish | |
Coating | Polyester powder-coated.Guidance for specification option: Standard finish. Wood effect.Guidance for specification option: High quality wood-grain at an additional cost. |
Texture | As Coating. |
Colour | Guidance for specification option: Various colours available. Consult manufacturer and insert requirement. |
Installation fasteners | Nine hooked dog bolts per leaf. |
Frame accessories | 100 mm lift off hinges, six per leaf.Grade 13 butt hinges, six per leaf. |
Door leaf | |
Thickness | 66 mm. |
Material | Magnelis.Manufacturer guidance1.5 mm thick. |
Glazing | |
Type | Not required.Vision panels, 203 x 356 mm.Guidance for specification option: Insert placement requirements, or drawing/ schedule reference. Vision panels, 203 x 762 mm.Guidance for specification option: Insert placement requirements, or drawing/ schedule reference. Vision panels, 457 x 457 mm.Guidance for specification option: Insert placement requirements, or drawing/ schedule reference. Manufacturer guidanceNote that vision panels reduce the doorset fire rating to FD60. |
Beading | |
Type | 10 mm astragal. |
Material | Steel. |
Finish | |
Coating | Polyester powder-coated.Guidance for specification option: Standard finish. Wood effect.Guidance for specification option: High quality wood-grain at an additional cost. |
Texture | As Coating. |
External colour | As Frame.Other.Guidance for specification option: Various colours available. Consult manufacturer and insert requirement. |
Internal colour | As External.Other.Guidance for specification option: Various colours available. Consult manufacturer and insert requirement. |
Film thickness (minimum) | Manufacturer's standard. |
Hardware | Not required.MICO 942 2/3 point locking systems.Guidance for specification option: Not fire rated. MICO USCH cylinder guard.Guidance for specification option: External access via MICO USCH cylinder guard with Scandinavian oval cylinders, as standard. Padlockable hasp and staple access device. |
Accessories | Not required.Stays and closers.Guidance for specification option: M100 and TS83, as standard. Removable top transom.Bladed louvre panel, 457 x 457 mm.Guidance for specification option: Note that doors with louvres are not fire rated. Fixed side panels.Fixed over panels.Removable over panels.Guidance for specification option: Note: Doors fitted with this option are not fire rated. |
Profile | 110 mm. Manufacturer guidanceFrame profile. |
Construction | Butt jointed frame sections. Guidance for specification option: Standard. Fully welded frame sections. Guidance for specification option: Fully welded frame, available at an extra cost. |
Panic hardware | Not required. MICO Elite panic escape. Guidance for specification option: Manual, automatic, or electromechanical deadlocking single point locking. |
Reinforcement | 3 mm chassis system. Guidance for specification option: No adjusters. |
Weight | 60 kg/m². Guidance for specification option: Approximate. Consult manufacturer for details based on exact specification. Manufacturer guidanceCirca. |
Lifting points | M10 lifting point per leaf. |
Hinges | 100 mm lift off hinges. 13 butt hinges. |