Standard manual control point, designed to allow the Fire & Rescue Service to manually override the smoke control system through a user-friendly interface.

Jump to:
+44 (0)1543 443060 Website

Application

Suitable for smoke ventilation applications.

Description

Standard manual control point, designed to allow the Fire & Rescue Service to manually override the smoke control system through a user-friendly interface.

Compatible with the OSLoop and OS2 control systems (specified separately).


Features and benefits:

  • Design includes an open button and a close/ reset button, which are accessed by lifting the clear front door.
  • Fully complies with pr EN 12101-9; provided in orange (RAL 2011), as required by this standard.
  • System status, operation, fault-finding and cable-monitoring are included within the features of the MCP (OSLoop version only), as required by the standard.
  • Can provide audible signals and faults, in addition to a silence button out-of-view.
  • The MCP (OSLoop version) continuously monitors actuators and connections to smoke detectors (as required by pr EN 12101-9).
  • Event-logging to provide historical user information.
  • Maintenance indication (statutory requirement of the Regulatory Reform Order – Fire Safety).
  • Cover reset push button via access key fob.
  • Reset push button.
  • Activated LED.
  • Power/ healthy LED.
  • Fault LED.
  • Single-action activation cover (replaces glass frangible element).
  • Made in Britain.
  • CE marked.

General information

Color

Orange

Guidance for specification option:

RAL 2011.

Finish

Smooth

Material

Plastic

Shape

Square

Length

87 mm

Width

54 mm

Height

87 mm

Uniclass

Pr_75_50_18_80 Smoke and heat exhaust control panelsPrimary

CAWS

S92/410 Sprinkler alarm panels

S92/410 Control panels

Specification data - Smoke and heat exhaust control panels

Mounting

Flush-mounted.

Surface-mounted.

Accessories

Not required.

Dumb reset key.

Surface mount box.

MCP finger plate.

Sustainability data

Country of product manufacture

United Kingdom

Literature