NBS Source
I'm a manufacturer

NORTEC L 38 x M - Raised Access Floor Panel

Verified by manufacturer 27 days ago

Lindner Group Third party certifications:
  • EPD

    EPD

    Certificate type

NORTEC floor panels are manufactured from calcium sulphate (gypsum): a non-combustible material, the panels are protected against shock and humidity by an edge trim on all edges.

Jump to:
020 8246 6333 Website

Application

  • Office areas, working areas and corridors: Commercial buildings, hospitals, surgeries.
  • Technical Rooms: Electrical distribution and switchgear cabinet rooms.
  • Areas with high foot fall: Educational facilities, restaurants.

Description

The raised access floor system NORTEC is the suitable product for nearly all applications with its excellent technical and building-physical characteristics.

The raised access floor panels consist of fibre-reinforced calcium sulphate. The panels are protected against shock and humidity by an edge trim on all edges. The substructure consists of height-adjustable zinc-coated steel pedestals from our own production which form the necessary cavity for installations and gaskets for sound decoupling.


Features and benefits:

  • Excellent walking comfortability.
  • Very high load-ability.
  • Non-combustible.
  • Simple lifting and exchanging of single panels.
  • Wide array of coverings.
  • Earthquake safety: International Building Code (IBC) available in A–F.
  • Cradle to Cradle Certified Silver.
  • Environmental product declaration to ISO 14025 and ISO 14021.

General information

Color

White

Finish

Other

Material

Calcium sulphate

Guidance for specification option:

Zinc-coated.

Steel

Shape

Other

Length

600 mm

Width

600 mm

Height

38 mm

Warranty description

25 year

Uniclass

Ss_30_20_70_70 Raised access floor systemsPrimary

CAWS

K41/130 Raised access floor

Product range

Lindner Raised Access Floor / NORTEC

Specification data - Raised access floor systems

Subfloor preparation

Guidance for specification option:

Consult manufacturer and insert requirements or omit.

Support structure type

Access floor pedestals, zinc-coated steel.

Guidance for specification option:

Pedestal distance: 600 x 600 mm.

Pedestal fixings

Guidance for specification option:

Consult manufacturer and insert requirements.

Raised access floor surface

Raised access floor panels.

Barriers in floor void

-

Fire barriers

Not required.

Solid Gypsum wall blocks.

Guidance for specification option:

Fire protection barriers made from solid gypsum wall blocks (min. 80 mm)

Acoustic barriers

Not required.

Foam mortar.

Guidance for specification option:

Sound protection barriers made from foam mortar (min. 100 mm).

Plenum barriers

Not required.

Coated chipboard panels.

Guidance for specification option:

Ventilation barriers made from coated chipboard panels.

System accessories

Not required.

Facings.

Expansion joints.

Electrical outlets.

Cavity barriers.

Air ventilation outlets.

Bridging profiles.

Reinforcement profiles.

Calculated weighted sound reduction index (Rw)

To ISO 140, 61 dB.

Fire resistance

To DIN 4102-2, F30, To DIN 4102-2, F60, To BS EN 13501-2, REI 30; To BS EN 13501-2, REI 60.

Load class

To EN 12825, 2A.

Manufacturer guidance

Load and deflection class.

Breaking load

To EN 12825, 6 kN.

Guidance for specification option:

Concentrated load 3 kN.

LoadSafetyFactor

To EN 12825, 2.

Thickness

38 mm.

Pedestal height

-

Manufacturer guidance

25–2000 mm. Insert requirements.

Weight

62 kg/m².

Manufacturer guidance

Approximately.

Impact sound reduction

12 dB without covering; 27 dB with covering.

Sustainability data

Contains Red List materials

No

Country of material origin

Germany

Country of product manufacture

Germany

Embodied carbon

A1-A3 (production stage) as defined in BS EN 15804

1.32 kg CO₂ eq/m

Recyclability

yes

Recycled content

As defined in clause 7.8 of BS EN ISO 14021

100 %

Third party certifications

Third party certifications

EPD

EPD

Raised Floor system, Type NORTEC

Literature

NORTEC L 38 Data sheet

NORTEC L 38 Data sheet

Lindner Group - Our Building Modules

Lindner Group - Our Building Modules

Case studies

MOL campus - Floor and more G40 and NORTEC

MOL campus - Floor and more G40 and NORTEC

Pôle d'Échange Serra -> Partitions -> Floors

Pôle d'Échange Serra -> Partitions -> Floors

HAUSER CB - Metal Ceilings, LIGNA and NORTEC raised floors

HAUSER CB - Metal Ceilings, LIGNA and NORTEC raised floors