Verified by manufacturer 27 days ago
EPD
Certificate type
NORTEC floor panels are manufactured from calcium sulphate (gypsum): a non-combustible material, the panels are protected against shock and humidity by an edge trim on all edges.
The raised access floor system NORTEC is the suitable product for nearly all applications with its excellent technical and building-physical characteristics.
The raised access floor panels consist of fibre-reinforced calcium sulphate. The panels are protected against shock and humidity by an edge trim on all edges. The substructure consists of height-adjustable zinc-coated steel pedestals from our own production which form the necessary cavity for installations and gaskets for sound decoupling.
Features and benefits:
Color | White |
Finish | Other |
Material | Calcium sulphate Guidance for specification option: Zinc-coated. Steel |
Shape | Other |
Length | 600 mm |
Width | 600 mm |
Height | 38 mm |
Warranty description | 25 year |
Uniclass | |
CAWS | K41/130 Raised access floor |
Product range |
Subfloor preparation | Guidance for specification option: Consult manufacturer and insert requirements or omit. |
Support structure type | Access floor pedestals, zinc-coated steel.Guidance for specification option: Pedestal distance: 600 x 600 mm. |
Pedestal fixings | Guidance for specification option: Consult manufacturer and insert requirements. |
Raised access floor surface | Raised access floor panels. |
Barriers in floor void | |
Fire barriers | Not required.Solid Gypsum wall blocks.Guidance for specification option: Fire protection barriers made from solid gypsum wall blocks (min. 80 mm) |
Acoustic barriers | Not required.Foam mortar.Guidance for specification option: Sound protection barriers made from foam mortar (min. 100 mm). |
Plenum barriers | Not required.Coated chipboard panels.Guidance for specification option: Ventilation barriers made from coated chipboard panels. |
System accessories | Not required.Facings.Expansion joints.Electrical outlets.Cavity barriers.Air ventilation outlets.Bridging profiles.Reinforcement profiles. |
Calculated weighted sound reduction index (Rw) | To ISO 140, 61 dB. |
Fire resistance | To DIN 4102-2, F30, To DIN 4102-2, F60, To BS EN 13501-2, REI 30; To BS EN 13501-2, REI 60. |
Load class | To EN 12825, 2A. Manufacturer guidanceLoad and deflection class. |
Breaking load | To EN 12825, 6 kN. Guidance for specification option: Concentrated load 3 kN. |
LoadSafetyFactor | To EN 12825, 2. |
Thickness | 38 mm. |
Pedestal height | Manufacturer guidance25–2000 mm. Insert requirements. |
Weight | 62 kg/m². Manufacturer guidanceApproximately. |
Impact sound reduction | 12 dB without covering; 27 dB with covering. |
Contains Red List materials | No |
Country of material origin | Germany |
Country of product manufacture | Germany |
Embodied carbonA1-A3 (production stage) as defined in BS EN 15804 | 1.32 kg CO₂ eq/m |
Recyclability | yes |
Recycled contentAs defined in clause 7.8 of BS EN ISO 14021 | 100 % |