Verified by manufacturer 16 days ago
Intelligent control of the indoor climate in the building.
Suitable for all building types, regardless of need and size.
The NV Embedded® controls solution uses intelligent control logic hosted on the control panels (also referred to as MotorControllers), which is configured to the specific building layouts and zone requirements. This software automatically controls the windows and indoor climate in each zone, according to desired setpoints and readings from the internal room sensors and external weather station. The system selects the window positions for a room according to sensor readings including temperature and CO2, taking into account wind, rain, and outdoor temperature readings from the weather station.
Features and benefits:
System performance | Indoor climate control. |
Objectives | Guidance for specification option: Insert requirements. |
Programme controls | Natural and mixed mode ventilation as well as heating, sun screening and cooling. |
Natural ventilation system | Ventilation inlets and outlets with automatic controls. |
Shutdown | Disable natural ventilation system. |
Night cooling signal | Operable windows or louvres being opened for a pre-set period of time over night. Guidance for specification option:
|
Normal operation | |
Operation | Manufacturer guidanceConsult manufacturer and insert requirements. |
Zone temperature set point | Manufacturer guidanceConsult manufacturer and insert requirements. |
CO2 concentration set point | Manufacturer guidanceConsult manufacturer and insert requirements. |
Outside air temperature | |
Operation | Manufacturer guidanceConsult manufacturer and insert requirements. |
Set point | Manufacturer guidanceConsult manufacturer and insert requirements. |
Control priority | Manufacturer guidanceConsult manufacturer and insert requirements. |
Rain operation | |
Action | Openings are closed on detection of rainfall. Guidance for specification option: Inbuilt safety function such that the window openings are closed during rainfall. |
Position (maximum) | Closed. |
Average wind speed | |
Operation | Limited to a safe operating position on detection of high wind speeds. |
Limit | Manufacturer guidanceInsert requirements. |
Wind speed and outside air temperature | |
Operation | Closed during strong winds. |
Minimum setting | Manufacturer guidanceConsult manufacturer and insert requirements. |
Set limits | Manufacturer guidanceConsult manufacturer and insert requirements. |
Set period | Manufacturer guidanceConsult manufacturer and insert requirements. |
Additional functions | Data logging. Guidance for specification option: Continuous logging and storage of all data concerning interior climate, weather conditions, window positions, etc. |
Equipment | MotorLink® window actuator. |
Sensors | WWS 100 Room sensor. Guidance for specification option: Temperature, CO2 and humidity sensor, with WSK-Link™. WSA 311 Smoke detector. |
Equipment interconnectivity | Wired. |
Control equipment power supply | Mains supply. Guidance for specification option: 230 V a.c. |
Control unit | MotorController type WCC 310/320 Plus and CompactSmoke™ panels type WSC 310/320 Plus. CompactSmoke™ panels type WSC 310/320 Plus. Manufacturer guidanceNV Embedded® consists of a WindowMaster MotorController and/ or CompactSmoke™ panels, from which WindowMaster indoor climate control logic can be activated by means of a USB dongle. |