Verified by manufacturer 18 days ago
DoP
Certificate type
Stone wool slab with reinforced aluminium foil facing.
Suitable for ventilation ducts and equipment.
Thermal insulation slab.
Features and benefits:
Surface temperature of the facing must not exceed 80°C (temperature restriction determined in accordance with heat resistance adhesive).
PAROC stone wool products are capable of withstanding high temperatures. The binder starts to evaporate when its temperature exceeds approximately 200°C. The insulating properties remain unchanged, but the compressive stress weakens. The softening temperature of stone wool products is over 1000°C.
Color | Silver |
Finish | Foil |
Material | Stone wool |
Shape | Rectangle |
Length | 1200 mm |
Width | 600 mm |
Uniclass | |
CAWS | U90/490 Site-applied insulation to ductwork U90/490 Site-applied insulation to ductwork |
Standard | To BS EN 14303. |
Form | Stone wool slabs. |
Thermal conductivity | 0.063 W/m·K at 50°C.Guidance for specification option: Also:
|
Finish | Aluminium foil-faced. |
Fire performance | To EN 14303:2009+A1:2013 (EN 13501-1), Euroclass A1. |
Insulation thickness (minimum) | 30 mm.Guidance for specification option: 30–100 mm. Manufacturer guidanceTo EN 823: |
Vapour barrier | |
Material | Aluminium. |
Vapour permeability | To EN 14303:2009+A1:2013 (EN 12086), MV2. |
Dimensions | 600 x 1200 mm. Manufacturer guidanceTo EN 822: |
Dimensional stability | To EN 14303:2009+A1:2013 (EN 14706), 250°C. |
Water absorption | ≤ 1 kg/m². |
Thickness tolerance | T5. |
NBS BIM Object Standard
This BIM object has been authored to meet the requirements of the NBS BIM Object Standard.
Find out more about the NBS BIM Object Standard.
Platform | Compatible | Version |
---|---|---|
- | 1 | |
- | 1 |