Verified by manufacturer 2 months ago
UL-EU Certified
Certificate type
Coated stone wool board used to form a penetration seal to reinstate the fire resistance performance of wall and floor constructions.
Used to reinstate the fire resistance performance of flexible and rigid walls and rigid floors where they have been penetrated by various cables, plastic pipes and metallic pipes.
Coated mineral wool board used to reinstate the fire resistance performance of wall and floor constructions where they have been provided with apertures for the penetration of single or multiple services. The panel is supplied coated on both faces. It is cut to size and friction fit into the aperture around the services.
PFC Corofil Coated Panel System is available in 1200 x 600mm panels, 50mm thick with a density of 140 kg/m³. PFC Corofil Acoustic Intumescent Sealant is required to seal all joints and junctions during the sealing process.
Features and benefits:
• Tested to EN 1366-3
• Provides fire resistance performance of up to 120 minutes integrity and insulation
• Can be installed in apertures up to 730mm wide and 1200mm high or 600 x 600mm depending upon the application
• For use with plastic pipes, metallic pipes, cables, cable trays and cable ladders
• 3rd party certification; UL-EU-01169-CPR
Material | Mineral fibre Guidance for specification option: Mineral fibre batt coated on both faces with a 1 mm-thick (nominal) white ablative coating. |
Shape | Rectangle |
Length | 1200 mm |
Width | 600 mm |
Height | 50 mm |
Uniclass | |
CAWS | P12/140 Fire-stopping system to multiple services penetrations |
Product range |
Board barrier | PFC Corofil Coated Panel - 50 mm thick. |
Fire performance | Up to two hours (120 minutes). Guidance for specification option: To EN1366-3:2009, up to two hours (120 minutes) dependent on wall or floor construction and services, consult manufacturer's literature for more information. UL-EU Certificate: UL-EU-01169-CPR. |
AcousticRating | RW (C:Ctr)= 24 (-2:-3). Manufacturer guidanceTo TR024 |
Country of material origin | United Kingdom |
Material | Mineral fibre Guidance for specification option: Mineral fibre batt coated on both faces with a 1 mm-thick (nominal) white ablative coating. |