Cold press pipeline fittings for use with copper gas pipes.
Suitable for gases, domestic and commercial liquid gas in the gas phase, heating oil pipelines, diesel fuel pipelines, compressed air systems.
Press connector fittings (d12-64) with connectors and pipes manufactured from copper, gunmetal and silicon bronze, in accordance with DIN EN 1057 and DVGW worksheet GW 392.
Suitable for:
Sealing element:
Hydrogenated nitrile butadiene rubber (HNBR) sealing element guarantees that the press connections have the required degree of sealing, even where the pipe surface is rough.
Press connectors:
The connection is made through a double press connection - both before and after the sealing element and permanently connected to the pipe during pressing. The sealing element is not deformed during pressing. Viega's distinctive hexagonal pressing pattern bonds fitting and pipe and provides the mechanical strength for the connection.
The connectors may only be pressed with Viega press machines with constant pressing force (i.e. Pressgun 6+, Picco 6+).
With SC‑Contur, any connections which remain un-pressed become visible when the system is filled. The SC‑Contur is certified and fulfils the requirements of DVGW worksheet G 5614, point 4.4.1, connectors with forced leakage.
Viega guarantees that unpressed connections are visible during a leakage test:
Viega Profipress G fittings are offered in various configurations, including:
Corrosion resistance:
Depending on the area of use, corrosion protection measures may be necessary. The manufacturer suggests over-ground pipelines and fittings in rooms which do not normally require external corrosion protection.
They suggest exceptions in the following cases:
The manufacturer recommends that the following regulations are followed:
The connectors may only be pressed with Viega press machines with constant pressing force (e.g. Pressgun 6+, Picco 6+, Pressgun 4E/ 4B).
Color | Copper |
Finish | Copper |
Material | Copper Gunmetal |
Length | Bespoke |
Width | Bespoke |
Height | Bespoke |
Warranty description | Six year |
Uniclass | |
CAWS | S90/150 Indirect hot water storage supply S90/140 Direct hot water storage supply S90/140 Direct hot water storage supply S90/120 Storage cold water supply S90/110 Mains cold water supply S90/160 Rainwater/ greywater recycling system S90/110 Mains cold water supply S90/130 Instantaneous hot water supply |
Product range |
Standards | |
Press fittings | Manufacturer's standard.Guidance for specification option: Press connector fittings manufactured from copper and silicon bronze for copper pipes up to 64mm in accordance with DIN EN 1057. The fittings shall be supplied and manufactured by Viega, equipped with the SC-Contur ‘leak before press’. SC-Contur guarantees the identification of non-pressed connections throughout the entire pressure range from 22 mbar to 3 bar with compressed air or inert gases. The fitting is double pressed; both in front and behind the HNBR sealing element. |
Type | Guidance for specification option: Consult literature and insert requirements [part number(s)]. |
Accessories | Guidance for specification option: Consult manufacturer and insert requirements. |
Sizes | 12 mm. Guidance for specification option: Press connectors with threaded connection manufactured from gunmetal. 15 mm. Guidance for specification option: Press connectors with threaded connection manufactured from gunmetal. 18 mm. Guidance for specification option: Press connectors with threaded connection manufactured from gunmetal. 22 mm. Guidance for specification option: Press connectors with threaded connection manufactured from gunmetal. 28 mm. Guidance for specification option: Press connectors with threaded connection manufactured from gunmetal. |
Operating temperature | Gas and liquid gas installations: -20°C to +70°C; Heating oil and diesel fuel installations: 40°C (maximum). |
Operating pressure (maximum) | Manufacturer's standard. Guidance for specification option: Gas and liquid gas installations: 0.5 MPa; At HTR-requirement 650°C/ 30 minutes: 0.1 MPa (1 bar). Heating oil and diesel fuel installations: -0.05 to +0.5 MPa. |
Contains Red List materials | No |
Country of material origin | Germany |
Country of product manufacture | Germany |
Embodied carbonA1-A3 (production stage) as defined in BS EN 15804 | 5.47 kg CO₂ eq/kg |