NBS Source
I'm a manufacturer

Prolight Continuous Rooflight

Verified by manufacturer 4 days ago

Mercor Fire Protection UK LTD

Continuous rooflights with optional smoke exhaust vents.

Jump to:
Website

Application

Suitable for warehouses, public services buildings, shopping malls, commercial and sport objects.

Description

mrc PROLIGHT continuous rooflights are designed to supply daylight to interiors. The rooflights can also be used in the natural smoke and heat exhaust systems due to installed smoke exhaust and ventilation vents or a combination of the former two types.

A wide range of mcr PROLIGHT rooflights enables the installation of a range of vents: from 100 x 100 cm to 200 x 250 cm (single leaf vents), and from 100 x 100 cm to 250 x 250 cm (double leaf vents).

The vents integrated in rooflight systems, in the case of smoke exhaustion function, can be additionally assembled with wind deflectors, which increases the surface of active smoke exhausting.

Features and benefits:

  • Continuous rooflights certified according to EN 14963, CE marked.
  • Smoke exhaust vents in rooflights are certified according to EN 12101-2, CE marked.
  • The structure allows a good value of heat transfer coefficient (U).
  • The range of additional elements includes anti-burglar grid, safety net and limit switch (for rooflights with smoke vents).

General information

Color

Grey

Material

Aluminium

Polycarbonate

Shape

Square

Rectangle

Length

1000 mm

2500 mm

Width

1000 mm

2000 mm

2500 mm

Uniclass

Pr_30_59_72_31 Framed rooflightsPrimary

CAWS

L10/490 Roof ventilators

L10/460 Rooflights

L10/45 Rooflights

Specification data - Framed rooflights

Classification data

Form

Barrel vault.
Triangular.
Pyramid.
Dome.

Size

-

Manufacturer guidance

Continuous rooflights with a span up to 6.0 m.

Wide scope of smoke vent sizes:

  • Single-leaf: 1000 x 1000 mm to 2000 x 2500 mm.
  • Double-leaf: 1000 x 1000 mm to 2500 x 2500 mm.

Insert requirements or refer to a drawing.

Product performance

-

Fire performance

-

Fire resistance

To PN EN 13501-5, Class Broof(t1).

Frame

-

Material

Aluminium.

Finish

-

Colour

RAL.

Guidance for specification option:

RAL palette colour selection for elements. Consult manufacturer and insert requirements.

Glazing or infill

-

Type

Multi-chamber polycarbonate sheet.

Guidance for specification option:

10–25 mm thickness.

Construction

Single skin.

Integral kerb

Aluminium.

Operation

-

Type

Not required.
Powered, electric.
Pneumatic.

Manufacturer guidance

By implementing the smoke exhaust function, the vents can be pneumatically or electrically controlled (24 V-). In ventilation vents, the electric actuator is used for their control (230 V~). Consult manufacturer's literature for details.

Control

Not required.
Weather monitoring unit, wind-rain sensor and push button.
Link to fire alarm system.

Accessories

Not required.
Anti-burglar grid.
Safety net.
Limit switch.

Guidance for specification option:

For rooflights with smoke vents.

Wind deflector.

Guidance for specification option:

For rooflights with smoke vents.

Standards

To EN 14963 and EN 12101-2.

Vent

Not required.
Smoke exhaust vents.
Ventilation vents.

Sustainability data

Material

Aluminium
Polycarbonate

Literature

PROLIGHT rooflighting systems

PROLIGHT rooflighting systems