NBS Source
I'm a manufacturer
Compare variants

Ranger 2 Cable (Standard and High Sensitivity) - Water Sensing Cable

Verified by manufacturer 4 months ago

Standard

Andel Ltd Variant:

Senses the presence of water and triggers an alarm that pinpoints the exact location.

Jump to:
+44 (0)1484 845000 Website

Application

Designed for a range of applications, including data centre floor voids, telecommunication rooms, HVAC equipment locations, pipes, electrical rooms, storage areas, tanks and roofs.

Suitable applications for the Standard cable include:

  • Below raised floors.
  • Above suspended ceilings.
  • Run in drip trays.
  • Laid around the base of plant, apparatus or tank.
  • Laid in loops or wave pattern for general monitoring of larger areas.

Suitable applications for the High Sensitivity cable include:

  • Attach to underside of pipes outside the lagging.
  • Above suspended ceilings.
  • Run in drip trays.
  • Fix to soffits and ceilings to detect water ingress.

Description

Floodline Ranger 2 sensing cables detect the presence of water at any point along their length. The cables are installed with a Floodline Ranger Leak Detection Panel, and when the cable senses water, it triggers an alarm and pinpoints the exact location.


The cable is small, lightweight and flexible, allowing for easy installation. The sensor can be wetted and dried any number of times provided the cable is not contaminated with a substance that permanently changes its electrical characteristics. If the contamination is soluble then the cable can be removed, washed (clean water only), dried and returned to use subject to the level of contamination.


Features and benefits:

  • Cable senses water presence and can pinpoint the exact location.
  • Provides distributed leak detection and location over a wide range of areas.
  • Available in a variety of lengths to provide as much coverage as needed.
  • Small, lightweight and flexible.
  • Easy installation.
  • Sensor can be wetted and dried multiple times.
  • Can be supplied with factory-installed metal connectors that plug together.
  • Tough four-core construction with protective outer braid.
  • The High Sensitivity cable has a fabric wrap under the outer braid.


Standards:

  • CPR (Construction Products Regulation) Testing.
  • Under the harmonised European standard EN 50575 this cable has been tested for heat release, smoke production and flame spread in accordance with EN 50399:2011+A1:2016 and EN 60332-1-2:2004+A11:2016.
  • Tested under AVCP (Assessment and Verification of Constancy of Performance) system 3 by a notified body the cable was classified as Euroclass Dca-s2,d0 (Standard) and Euroclass Eca (High Sensitivity).

General information

Color

White

Material

Polymeric

Polyester

Fabric

Shape

Other

Length

Bespoke

Width

6 mm

Warranty description

Ten year

Uniclass

Pr_75_50_48_96 Water-sensing cablesPrimary

Specification data - Water-sensing cables

Liquid to be detected

Water.

Resettability

Required.

Guidance for specification option:

If the contamination is soluble then the cable can be removed, washed (clean water only), dried and returned to use subject to the level of contamination.

Cable length

To suit the application.

Guidance for specification option:

Available between 5 and 15 m lengths. Insert requirement.

Leak location accuracy

+/- 1 m.

Accessories

Not required.

Factory installed metal connectors.

Construction

Four core, all polymeric construction with protective outer braid.

Diameter

6 mm.

Fixing

Standard 6 mm tower clips, self-adhesive clips or tie- wraps.

Sustainability data

Contains Red List materials

No

Country of material origin

United Kingdom

Country of product manufacture

United Kingdom

Material

Polymeric

Polyester

Fabric

Literature

Ranger 2 Cable

Ranger 2 Cable

Ranger 2 High Sensitivity Cable

Ranger 2 High Sensitivity Cable