Verified by manufacturer 2 months ago
BS EN 13501-2:2023
Certificate type
Insulated fire protection system for protection of shafts and voids in multi-storey buildings with a rapid installation system preventing continuous routes for the spread of fire.
Protection of shafts and voids in multi-storey buildings with a rapid installation system preventing continuous routes for the spread of fire.
EI60 Shaftwall System with 25 mm glass mineral wool insulation, classified to EN 13501-2:2016.
Color | Pink |
Finish | Smooth |
Material | Plasterboard Steel Glass mineral wool |
Width | Bespoke |
Height | Bespoke |
Warranty description | Lifetime Guidance for specification option: Etex Building Performance Limited offers both a comprehensive Lifetime System Warranty (excl. Aqua Board and Weather Defence) and 10 Year Warranty (Incl. Aqua Board and Weather Defence). For full details see the full Warranty and Proprietary Systems Policy at www.siniat.co.uk/knowledge-centre/. Etex Building Performance Limited warrants to the purchaser that the Siniat Plasterboard Solutions (“Systems”) as originally designed, built and unaltered will perform to the original laboratory performance parameters as set out in the Siniat Drywall Manual and other relevant literature as published by Siniat. The system must be constructed solely with the proprietary products and components as supplied by Siniat. The system must be installed by a professional installer in accordance with: the Siniat Drywall Manual; this specification document; CAD drawings; advice; and all relevant and applicable construction standards and regulations. |
Uniclass | |
CAWS | K10/125 Metal stud partition system K10/30 Metal stud |
System performance | All Siniat systems should be constructed to BS 8000-8:2023 'The Standard for Workmanship on construction sites - Design and installation of dry lining systems. Code of practice.' |
Framing | 60 mm Siniat CH Studs CHS1960/B at 600 mm centres. |
Insulation | Glass mineral wool, 25 mm. |
Linings | Face A Plasterboard Linings - Inner Layer: 19 mm Siniat Fire Core Board. |
Fasteners | Face B Inner Layer Fixing: 25 mm Siniat Self Tapping Screws at 600 mm centres. |
Joint treatment | Decorative.Guidance for specification option: Outer layer room side boards to be taped and jointed using appropriate Siniat compounds and tape. Non-decorative.Guidance for specification option: Outer layer room side boards to be taped and jointed using appropriate Siniat compounds and tape to at least first stage (bedding). |
System accessories | Siniat Flat Strap FS50/Rx.Guidance for specification option: For use where partition height exceeds board height; to be fixed behind all horizontal joints to provide substrate for board fixing. |
Fire resistance | To EN 1364-1: 60 minutes. |
Partition height | Cold state: 4800 mm. |
Sound insulation | 46 dB. |
Duty rating (to BS 5234-2) | Severe. |
Thickness: | 85 mm. |
Sealing (joints and penetrations) | Siniat Intumescent Acoustic Sealant. Guidance for specification option: Apply continuous beads of Siniat Intumescent Acoustic Sealant around the perimeter of the framing or to the edge of outer layers of board, ensuring that all air-paths are sealed. All penetrations should use supporting constructions detailed in the Siniat Drywall Manual unless superseded by specific test information. For combined, warrantied performance specify FSi fire-stopping products. For cPVC pipe sealing, use FSi PYROPRO® HPE Sealant in place of Siniat Intumescent Acoustic Sealant. |
System code | CH60B-19FC#212F |
Standards | All products are CE marked and UKCA marked in accordance with Construction Products Regulation where relevant standards or European Technical Approvals exist. All boards to conform to BS EN 520 or alternative standard where appropriate. Metal framing components are hot-dipped galvanized steel to BS EN 10346. Metal sections rolled to BS EN 10162. Metal studs, tracks and accessories conform to BS EN 14195 where required. Drywall screws conform to BS EN 14566. |
Sealer coat | Siniat Drywall Sealer. |
Country of material origin | Spain Guidance for specification option: Applies to the bulk material (gypsum) only. Other components are from other countries. Consult manufacturer for details. |
Country of product manufacture | United Kingdom Manufacturer guidanceUK applies to the majority of manufacture but a small percentage of finished items are imported. Contact manufacturer for details. |
Material | Plasterboard Steel Glass mineral wool |
Embodied carbonA1-A3 (production stage) as defined in BS EN 15804 | Manufacturer guidanceLatest EPD information available from: https://www.siniat.co.uk/en-gb/documentation/ |
Recyclability | Gypsum and metal components can be recycled depending on the segregation of all materials. |
Recycled contentAs defined in clause 7.8 of BS EN ISO 14021 | Manufacturer guidanceGypsum average 33.5% and metal average 17%. |
Platform | Compatible | Version |
---|---|---|
- | 1 |
Siniat A1 Shaftwall System – CH14B-19WD#312WD
Siniat A1 Shaftwall System – CH90B-19WD#312WD
Siniat EI120 Shaftwall System – CH14B-19FC#315F-25G
Siniat EI120 Shaftwall System – CH60B-19FC#315F-25G
Siniat EI120 Shaftwall System – CH90B-19FC#315F-25G
Siniat EI60 Shaftwall System - CH60B-19FC#212F
Siniat EI60 Shaftwall System – CH14B-19FC#212F
Siniat EI60 Shaftwall System – CH14B-19FC#212F-25G
Siniat EI60 Shaftwall System – CH90B-19FC#212F
Siniat EI60 Shaftwall System – CH90B-19FC#212F-25G