Verified by manufacturer 2 months ago
Steel - Polyester lacquer
Partition with a metal facing and mineral wool core.
The SM60 partition is designed for ultra-clean rooms which must be kept completely free of microbiological contamination. The partition consists of non-combustible modular panels, 60 mm thick, manufactured from time-stable materials and no emitting particles. The partition provides smooth surfaces which are easy to clean, are airtight and offer good insulation.
Profiles integrated into the thickness of SM panels allow the assembly of panels and the passage of cables. The system uses an aluminium key profile that is inserted into the full-length grooves on both sides of the wall panels.
Features and benefits:
Components:
Color | White |
Finish | Polished Lacquered |
Material | Metal Guidance for specification option: Stainless steel or steel facings. Mineral wool |
Shape | Rectangle |
Length | 4000 mm 6000 mm |
Width | 200 mm 250 mm 350 mm 550 mm 800 mm |
Uniclass | |
CAWS | K30/10 Relocatable partition system K30/130 Relocatable partition system K30/135 Relocatable partition/ ceiling system |
Panel partitioning | Partition panels. |
Joint treatment | Bi-component polyurethane adhesive. |
Joint finish | Silicone sealant (quality-label SNJF; complies with FDA 21 CFR 175.105). |
Width | 200 mm. 250 mm. 350 mm. 550 mm. 800 mm. |
Panel length | 4000 mm. 6000 mm. |
Facing | Steel sheet S280 GD, hot-dip galvanized Z225. Guidance for specification option: 225 g/m² of zinc on the two faces or similar. |
Sheet facing thickness | 0.5 mm. 0.6 mm. Guidance for specification option: Standard. 0.8 mm. |
Colour/ Finish | Polyester 25 μm lacquer. Guidance for specification option: Class in accordance with XP P 34-301: lIIa. |
Thickness | 60 mm. |
Profile | Metallic profile for passage of cables. |
ThermalConductivity | 0.041 W/m.°C. Manufacturer guidanceThermal conductivity coefficient lambda. |
ThermalTransmittance | 0.612 W/m².°C. Manufacturer guidanceThermal transmission coefficient Uc. |
R-Value | 1.6. |
Weight | Weight 17 kg/m² (two faces, 0.6 mm thick). |
Air tightness | Qs ≤0.0027 m³/h.m² under ΔP: 50 Pa. Manufacturer guidanceTightness in the whole partition with silicone joint. |
Reaction to fire | Euroclass A2-s1,d0 and Class 0 to BS 476-6 and BS 476-7. |
SurfaceSpreadOfFlame | To ASTM E84-01, Class 1; to BS 476-6, 0.7; to BS 476-7, Class 1. Manufacturer guidanceFlame spread, flame spread index. |
Approvals | FM Global approval: FM Approvals (standard 4880) = Class 1; UL approval (cable routing) Safety E471046. |
Country of product manufacture | France |
Recycled contentAs defined in clause 7.8 of BS EN ISO 14021 | 12 % |