An electrically operated active smoke barrier used to form a virtually continuous barrier against fire effluent.

Jump to:
BOS
+44 (0)23 9245 4405 Website

Application

Suitable to be used to form a virtually continuous barrier against smoke.

Description

An electrically operated active smoke barrier assembly. Smoke barrier assemblies comprises a metallic fabric, fan-folded and retained in a metal tray, powered by an internal 24 V d.c. electric motor, enclosed within a 1.2 mm-thick steel box. A special bottom tray is fitted to the bottom of the curtain providing tension to the curtain with sufficient weight for the curtain to ‘fail-safe by gravity’.


The edges of the curtain are retained inside side guides, providing pressure resistance of 20 Pa. The 24 V motor contains an electromagnetic brake to arrest motion of the curtain when in the open position. Barrier assemblies have been tested to the requirements of EN 12101-1, Annex B for ‘Reliability and response times’ (1000 cycles on primary power and an additional 50 cycles using back-up power; closing speed of 0.07 m/s). Barrier assemblies have been tested to the requirements of EN 12101-1 for ‘Temperature/ time resistance’ (120 minutes' integrity).


The fabric used in the barrier assemblies have a Reaction to Fire Classification of ‘A1’.


Operation:

Barrier assemblies commences movement upon initiation of alarm or power or system failure, and fully deploy to the fire operational position within the range of velocities of 0.06 m/s to 0.15 m/s using the unique VarioSpeed™ function. Operating speeds are site adjustable without altering the bottom bar mass. Speeds may be dictated by those authorities having jurisdiction for ‘safety in use’ according to the location, nature or function of each unit.


In the event of a mains supply power failure, the curtain is retained in the open position for a pre-determined period (nominally 30 minutes), using battery back-up power. At the end of the period, the barrier assembly will deploy.


Period of fire resistance:

60 minutes' integrity.

General information

Color

Other

Finish

Galvanized

Material

Fabric

Guidance for specification option:

Metallic fabric.

Shape

Circle

Length

Bespoke

Width

Bespoke

Height

Bespoke

Warranty description

One year

Guidance for specification option:

From date of commissioning.

Uniclass

Pr_25_80_79_01 Active smoke barriersPrimary

CAWS

L20/610 Roller shutters/ curtains

Specification data - Active smoke barriers

Standard

BS EN 12101-1:2005+A1:2006, BS EN 1363-1:1999, BS EN 1634-3, BS EN 13501-4:2007+A1:2009, BS EN ISO 1716:2010, BS EN 13823:2010, BS EN 13501-1:2007+A1:2009, BS 476-6:1989+A1:2009, BS 476-7:1997, BS 6323-5:1982.

Third-party certification

To BS EN 12101.

Classification categories

DH60, A1.

Material

Flexible metallic fabric.

Guidance for specification option:

  • The main curtain fabric type is EFP™ A1, which is a stainless steel wire reinforced glass fabric fire barrier. It has an area weight of 665 g/m² -5%, + 10%.
  • The curtain fabric offers dimensional stability and is non-combustible to BS EN 13501-1 + A1– Reaction to Fire.
  • The fabric has passed testing to BS 476-6 (Method of test for fire propagation for products).
  • The fabric has passed testing to BS 476-7 (Method of test to determine the classification of the surface spread of flame for products).
  • The fabric has passed testing to BS EN 1634-1, BS EN 1363-1, BS EN 1362-2 and BS EN 1634-3 (Fire/Smoke Resistance)
  • The fabric has passed testing to BS EN ISO 1716 (Determination of the Heat of Combustion for Building Products).
  • The fabric has passed testing to BS EN 13823 (Reaction to Fire Tests – Single Burning Item)
  • The fabric has passed testing to HSG 248 (Analysis of Material for the presence of Asbestos).
  • The fabric has passed testing to BS EN 14184-1 (Textiles – Determination of Formaldehyde – Part 1: Free and hydrolysed formaldehyde (water extraction method).

Opening sizes

Bespoke.

Guidance for specification option:

Consult manufacturer and insert requirement.

Accessories

None.

DH60, A1.

Beam protection and obstruction warning.

Emergency retract.

Split drop delay.

Show more

Fire resistance

60 minutes integrity.

Motor

24 V d.c. electric motor.

Sustainability data

Contains Red List materials

No

Country of material origin

United Kingdom

Country of product manufacture

United Kingdom

Recyclability

Coopers Fire offer a take back service where product is broken down into component parts.
Metal = recycled
Fabric = recycled
WEEE = disposed through correct channels

Recycled content

As defined in clause 7.8 of BS EN ISO 14021

0 %

BIM objects

BOS

NBS BIM Object Standard

This BIM object has been authored to meet the requirements of the NBS BIM Object Standard.

Find out more about the NBS BIM Object Standard.

Platform Compatible Version
Revit

Revit 2017

1

IFC
-

1

Third party certifications

Warrington Fire

Warrington Fire

SMOKESTOP CONCERTINA “CLOSED” SMOKE CURTAIN

Literature

Examples of FireMaster and SmokeStop Concertina Installations

Examples of FireMaster and SmokeStop Concertina Installations

Case studies

Battersea Power Station, London

Battersea Power Station, London