Verified by manufacturer 3 months ago
Double leaf natural smoke and heat exhaust ventilator.
Suitable for commercial applications.
The Double Leaf (NSHEV) UDF-50REM Smoke and Heat Exhaust Ventilator is fitted with solid, insulated covers and electric actuation for remote opening and closing.
The kerb is 305 mm in height with integral capflashing, 50 mm polyisocyanurate insulation with a U-value of 0.47 W/m²K, fully-welded at corners, and 114 mm mounting flange with 11 mm holes provided for securing frame to the roof deck.
Features and benefits:
Finish | Mill |
Material | Aluminium Polyisocyanurate |
Shape | Rectangle |
Length | 1848 mm |
Width | 1728 mm |
Height | 305 mm Guidance for specification option: Curb 305 mm in height formed with a 114 mm flange. |
Warranty description | Five year Guidance for specification option: Manufacturer's warranty. |
Uniclass | |
CAWS | L10/490 Roof ventilators |
Standard | To BS EN 12101-2. |
Mounting | Roof-mounted. |
Aerodynamic free area | 1.5 m². |
Reliability classification | Re 1000.Guidance for specification option: 10,000 when used as a day to day ventilator. |
Snow load classification | SL 500. |
Low ambient temperature classification | T (-15). |
Wind load classification | WL 1500. |
Arrangement | Flap. |
Dimensions | |
Length | Overall: 1848 mm; Internal: 1620 mm. |
Width | Overall: 1728 mm; Internal:1500 mm. |
Controls | Not required.1RPREM-01.Guidance for specification option: Control Panel Kit (Control Panel, MCP, and Smoke Detector). 1RPREM-02.Guidance for specification option: MCP. 1RPREM-03.Guidance for specification option: Smoke detector. 1RPREM-04.Guidance for specification option: Thermostat. 1RPREM-07.Guidance for specification option: Auto/ manual control switch. 1RPREM-08.Guidance for specification option: Open/ close smoke vent switch, keyed. 1RPREM-08A.Guidance for specification option: Open/ close smoke vent switch, paddle. 1RPREM-09.Guidance for specification option: OS2 control panel. 1RPREM-10.Guidance for specification option: Open/ close switch. 1RPREM-11.Guidance for specification option: Weatherproof open/ close switch. 1RPREM-15.Guidance for specification option: Rain sensor. 1RPREM-21Guidance for specification option: MCP with break glass. |
Materials | |
Integral upstands | |
Material | Double-skin aluminium, insulated.Guidance for specification option: 3 mm aluminium, 50 mm thickness polyisocyanurate. |
Finish | Mill finish. |
Seals | Heavy extruded EPDM rubber gasket bonded to the cover interior to ensure a continuous seal when compressed to the top surface of the kerb. |
Curb | Curb liner. Flanged apron. Fully enclosed. Standard. |
Explosion relief smoke vent | Not required. Required. |
Cover | 3 mm aluminium with a 100 mm beaded flange with formed reinforcing members. 50 mm thick polyisocyanurate insulation, U-value 0.47 W/m²K. |
Maximum live load | Covers reinforced to support a minimum live load of 195 kg/m². |
Deflection | 1/150th of the span (maximum). |
Operating | Two 24VDC, battery backed linear actuators per cover (four actuators total) capable of opening the cover to the fire open position of 90º within 60 s and be capable of closing the covers. |
Hardware | Heavy pintle hinges provided. Curb mounted junction box (2 no.) with terminal blocks enclosed for power cable connection. |
Material | Aluminium Polyisocyanurate |