Verified by manufacturer 4 months ago
UE001 - rated steam production: 1.5 kg/h
Watermark
Certificate type
Immersed electrode humidifiers which are designed to generate safe steam humidification for duct, in-room, or steam bath application.
humiSteam basic (Y):
humiSteam X-plus (X):
humiSteam Wellness (W):
Immersed electrode humidifiers which are designed to generate safe steam humidification for duct, in-room, or steam bath application. This unit is designed to work with mains water supply with a conductivity level between 75 μS and 1250 μS.
Mains water contains a certain quantity of dissolved mineral salts and is slightly conductive therefore the principle of these units relies on applying voltage to metal electrodes immersed in the water which in turn creates an electric current flow that heats the water until producing steam.
Features and benefits:
Certifications:
CE, ETL (UL998), TÜV and EAC.
Color | Silver |
Finish | Galvanized Guidance for specification option: Housing. |
Material | Metal Guidance for specification option: Housing. |
Shape | Rectangle |
Length | 365 mm 545 mm 635 mm 1150 mm |
Width | 275 mm 375 mm 465 mm Manufacturer guidanceUnit depth. |
Height | 712 mm 815 mm 890 mm |
Warranty description | Two year Guidance for specification option: Materials warranty (from the manufacture date, excluding consumables). |
Uniclass |
Electrical supply type | Single phase, 208 V a.c., 50/ 60 Hz (U).Single phase, 230 V a.c., 50/ 60 Hz (D).Manufacturer guidanceVoltage: 10 to -15%. Other voltages available on request, consult manufacturer for details. |
Steam source | Electrode boiler (immersed electrodes). |
Material | Galvanized metal housing. |
Access doors for maintenance | Manufacturer's standard. |
Accessories | None.DP/*R0 lance for duct (standard).DP/*RU lance for duct (high capacity).DP/*RH lance for duct (high efficiency).SDP steam nozzle, 12 mm hole.SDP steam nozzle, 22 mm hole.SDP steam nozzle, no hole (to be drilled).Hoses.Guidance for specification option: Consult manufacturer for options and insert requirements. Probe - DPW* wall sensor.Probe - DPP* sensor for industrial environments.Probe - DPD* duct sensor.Probe - ASET* temperature sensor for steam baths.Fan blower, VS*.Fan blower, VR*.Manufacturer guidancePlastic. Up to 15 kg/h. Steam inlet suitable for 22 and 30 mm diameter. |
Dimensions | 365 x 375 x 712 mm. Manufacturer guidanceLength x width (depth) x height. |
Weight | 16.6 kg. |
Connection | Standard; code 0. |
Network type | Modbus®. Guidance for specification option: Standard (built in). BacNET RS485. BacNET Ethernet. Modbus Ethernet. LON. |
Steam | Rated production: 1.5 kg/h. |
Power consumption | 1.12 kW. |
Connections | Steam: 22/ 30 mm diameter. |
Pressure | Outlet pressure limits: 0–1500 Pa. |
Cylinders | Standard; code 0. Standard cleanable; code C. For low conductivity; code 1. For low conductivity, cleanable; code 2. Manufacturer guidanceOne cylinder. |
Conditions | Operating: 1 to 40°C, 10–60% relative humidity. |
Ingress protection | IP20. |
Model | Basic (Y). Guidance for specification option:
X-plus (X). Guidance for specification option:
Wellness (W). Guidance for specification option:
|
Water | Fill: |
Fan | One blower, type VSDU0A; rated air flow: 288 m³/h. Guidance for specification option: Power supply: 24 V a.c. Rated power: 46 W. |
Classification | European version, code 01. UL certified version, code U1. China and APAC market version, code C1. |
Platform | Compatible | Version |
---|---|---|
- | 1 |