Verified by manufacturer 4 months ago
ViUV-MAP-S0 Master Panel
UL Certified
Certificate type
A distributed wall-mounted, panel-based voice alarm and fire telephone solution.
Suitable for a wide range of applications from small standalone buildings through to multi-story and campus style building complexes.
Chassis mounted electronics allowing first fix of cabinets and easy install.
Unicorn Voice is a distributed wall-mounted, panel-based voice alarm and fire telephone solution that is compliant with EN 54-16. Unicorn Voice simplifies the specification and installation of voice alarm and fire telephone systems by offering a one-cabinet solution. Comprising a range of master amplifier panels, distributed amplifier panels, desk microphones, wall microphones and remote volume controls. Additionally, the system can be supplied without EVC capability.
A Unicorn Voice system typically consists of a master amplifier panel for site control, networked with either further MAP/MAP-T panels or distributed amplifier panels DAP/DAP-T. This system architecture provides for expansion for small to large sites.
The MAP is equipped with everything required for a voice alarm system including amplifiers, message module, power supply, space for integral standby batteries and a microphone so live announcements can be made.
Features and benefits:
Color | Grey Guidance for specification option: RAL 7026 Graphite Grey back box finish. |
Material | Steel |
Shape | Rectangle |
Length | 220 mm Guidance for specification option: Depth. |
Width | 500 mm |
Height | 740 mm |
Warranty description | 18 months |
Uniclass | |
CAWS | W53/115 Emergency voice communication systems |
Standard | To EN 54-16. |
Rated voltage | 100–240 V a.c., 50/ 60 Hz. |
Output voltage | 70 V, 100 V.Guidance for specification option: Loudspeaker. |
Frequency response at rated power output | 70 Hz to 14 kHz. |
Connection ports | |
Audio inputs | One no. BGM, one no. front panel microphone, one no. external microphone, four no. fire input-opto-isolated sounder circuit with optional pull up, one no. reset input, four no. auxiliary inputs. |
Audio outputs | 256. |
Controls | |
Display type | 7” TFT touchscreen. |
Display the following conditions | AC, DC, PSU Status, General, CPU fault, VA, EVC Status.Guidance for specification option: Statutory indicators. |
Enclosure | |
Material | Steel. |
Colour | RAL 7026 Graphite Grey. |
Ingress protection (minimum) | IP3X. |
Environmental requirements | Operating: -5°C to +40° C, Humidity range: 0 to 80% non-condensing. |
Mounting method | Wall. |
Ancillary equipment | Not required.HS: Add Hot Swap (standby) amplifier.Guidance for specification option: Add HS to end of part code. S16: Add 16 switches to master panel.Guidance for specification option: Replace S0 with S16. S32: Add 32 switches to master panel.Guidance for specification option: Replace S0 with S32. S48: Add 48 switches to master panel.Guidance for specification option: Replace S0 with S48. S64: Add 64 switches to master panel.Guidance for specification option: Replace S0 with S64. S80: Add 80 switches to master panel.Guidance for specification option: Replace S0 with S80. S96: Add 96 switches to master panel.Guidance for specification option: Replace S0 with S96. S128: Add 128 switches to master panel.Guidance for specification option: Replace S0 with S128. VIUV-SPT.Guidance for specification option: A-B loudspeaker splitter module (maximum one per amplifier). VIUV-CMI.Guidance for specification option: Galvanically isolated copper network interface. VIUV-SMI.Guidance for specification option: Single-mode fibre interface network module. VIUV-MMI.Guidance for specification option: Multi-mode fibre interface network module. VIUV-AMP-25.Guidance for specification option: 25 W complete amplifier assembly. VIUV-AMP-50.Guidance for specification option: 50 W complete amplifier assembly. VIUV-AMP-100.Guidance for specification option: 100 W complete amplifier assembly. Manufacturer guidanceFactory fit options and optional modules. Add code to part code when ordering. For example ViUV-MAP-T-S128-Q100-HS. |
Cable entry | 30 x knockouts top, 24 x rear, 2 x mains. |
Cable | Network: Copper 2 x 2 core 1.5 mm screened fire rated, Single-mode fibre 9/ 125 μm, Multi-mode fibre 62.5/ 125 μm. |
AudioAmplification | Quantity: Up to 4. |
Dimensions | 740 x 500 x 220 mm. Guidance for specification option: H x W x D. |
Weight | 30 kg (maximum). Guidance for specification option: Without batteries. |
Contains Red List materials | No |
Country of material origin | United Kingdom |
Country of product manufacture | United Kingdom |